beautypg.com

Water piping — low temp systems, Gold cgs gas-fired water boiler, Valve adjustment – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 22: System-bypass piping method

background image

Part number 550-110-260/0200

22

GOLD

CGs

Gas-Fired Water Boiler

Water piping —

low temp systems

3f

1. Start with valve

7a

fully closed and

7b

fully open.

2. Gradually open valve

7a

while closing valve

7b

until the temperature at gauge

8

reads at

least 130 °F at all times.

3. Valve

7a

regulates the amount of boiler supply water mixed with return water. Valve

7b

causes a pressure drop in the system needed to balance flow through valve

7a

and the

system.

4. The valve adjustment should be done with the system at the coldest expected temperature

(60 °F for converted gravity systems or high mass radiant systems).

Valve adjustment

This piping method is called a

system-bypass

because part of the circulator flow bypasses

the system (through valve

7a

). This bypassed hot water from the boiler outlet mixes with

cooler system return water temperature in order to provide minimum 130 °F return water to
the boiler. Valve

7b

will most often be full open, but may need to be slightly closed on some

low pressure drop systems in order to cause enough flow through valve

7a

.

Figure 12

is an alternative piping method that provides return water temperature control for

boilers installed on

converted gravity systems

(large water content or steam systems).

Do not

apply the piping of

Figure 12

on

radiant heating systems

. It provides no method

regulating the water temperature provided to the system and could result in excessive water
temperature in the radiant tubing.

System-bypass piping as shown in

Figure 12

can be used with either zone valve or circulator

zoning. When used with circulator zoning however, the boiler circulator (item

3

), must be

piped as shown. It cannot be used as one of the zoning circulators.

Do not apply system-bypass piping if the reduced flow in the system could cause poor heat
distribution. That is, system-bypass piping reduces the flow in the system and increases the
water temperature supplied to the system. This can cause increased heat from radiators at the
beginning of the system and reduced heat from radiators near the end of the system.

System-bypass

piping method

Failure to

prevent low return water temperature

to the boiler could cause corrosion of

the boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.

Radiant heating system piping should include a means of

regulating the boiler return

water temperature

and the

system supply temperature

(such as provided by an

injection

pumping control

).

Boiler return water temperature will be adequately controlled using the methods shown in
this manual provided the

system supply temperature is relatively constant

.

DO NOT

apply the methods of this manual if the system is equipped with an

outdoor

reset control

. Instead,

provide controls and piping

which can

regulate the boiler return

water temperature

at

no less than 130 °F

regardless of system supply temperature. Contact

your Weil-McLain representative for suggested piping and control methods.

Failure to

prevent cold return water temperature

to the boiler could cause corrosion

damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.