Primary/secondary (preferred) bypass piping, Boiler manual, For radiant heating or converted gravity systems – Weil-McLain GOLD CGS 550-110-260/02002 User Manual

Page 19

background image

Part number 550-110-260/0200

19

Boiler Manual

primary/secondary (preferred) bypass piping —

for radiant heating or converted gravity systems

1

Boiler isolation (balancing) valves

2

Flow/check valve

3

System or zone circulator

4

System temperature gauges

5

Zone valve

6

Drain valve

7

System temperature valves (see instructions to the
left for adjusting valves)

8

Blend temperature gauge

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion
tank).

DO NOT

use an automatic air vent when using

closed-type expansion tank. It would allow air to leave
the system, causing waterlogging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if
used (For closed-type expansion tank, pipe from top
of air separator to tank fitting as in

Figure 5

.)

13

Air separator and automatic vent, if used (Note that
the fill valve must always be connected to the expansion
tank, regardless of location of expansion tank,
circulator or air separator.)

Figure 8

Zoning with circulators

Figure 9

Zoning with zone valves

26014

10

ZONE 2

ZONE 1

1

1

1

13

1

2

2

4a

4b

3

6

6

7b

7a

8

12"

MAX.

Cold

water

fill

11

12

9

Alternate
circulator
location

26015

10

Cold

water

fill

11

12

9

ZONE 2

ZONE 1

12"

MAX.

1

1

1

1

5

4a

4b

3

6

6

8

7b

13

7a

Alternate
circulator
location