Ez-zone – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 7
Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
5
•
C h a p t e r 1 O v e r v i e w
EZ-ZONE
®
PM Integrated Model 1/16 DIN with Remote Set Point — Input/Output
(no communications options 2 to 3)
Universal Sensor Input, Configuration Communications,
Red/Green 7-Segment Display
Supervisory
&
Power
Board
Slot C
PID
Controller
Board
Slot A
ramp-soak
with 4 files
(optional)
Output 4 none, switched dc, form A
mechanical (5 A) or solid-state (0.5 A)
relay
Output 3 none, switched dc/open
collector, form C mechanical (5 A) or
solid-state (0.5 A) relay, process (V, mA)
Output 2 none, switched dc, no-arc
power control (15 A), form A mechanical
(5 A) or solid-state (0.5 A) relay
Output 1 none, switched dc/open
collector, form C mechanical (5 A) or
solid-state (0.5 A) relay, process (V, mA)
off, heat, cool,
duplex, alarm,
retransmit,
event
off, heat, cool,
alarm, event
off, heat, cool,
alarm, event
EZ Key
programmable event
Digital Output (or Input) 5 (optional)
none, switched dc
Digital Output (or Input) 6 (optional)
none, switched dc
off, heat, cool,
alarm, event
off, heat, cool,
alarm, event
Network
remote user interface,
personal computer,
programmable logic
controller, human-
machine interface
EIA 485 Communications
Standard Bus, Modbus RTU (optional)
Remote Set
Point
Board
(optional)
Slot B
Analog Input 1 thermocouple,
RTD, process (V, mV, mA, 1k po-
tentiometer)
Digital Input (or Output) 5
(optional)
none, switch, volts dc
Digital Input (or Output) 6
(optional)
none, switch, volts dc
none,
idle set point,
alarm reset,
tune,
silence alarm,
manual/auto mode,
control outputs off,
local-remote,
lock keypad,
force alarm,
TRU-TUNE+
®
disable
loop & alarms off,
profile disable,
profile hold/resume,
profile start,
profile start/stop,
restore user settings
input sensor
input sensor
Input
Functions
Output
Functions
Analog Input 2 thermocouple,
RTD, process (V, mV, mA, 1k po-
tentiometer)
off, heat, cool,
duplex, alarm,
retransmit,
event
Remote Set Point Operation
•
Supports efficient set point manipulation from a remote device, such as a master control or PLC.