beautypg.com

Output 2 solid-state relay, form a, Output 3 switched dc/open collector, Output 3 mechanical relay, form c – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 21

background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

1 9

C h a p t e r 2 I n s t a l l a n d W i r e

Ó

Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.

Note:
Maximum wire size termina-
tion and torque rating:
• 0.0507 to 3.30 mm2 (30 to
12 AWG) single-wire termi-
nation or two 1.31 mm2 (16
AWG)
• 0.8 Nm (7.0 lb.-in.) torque

Note:
Adjacent terminals may be
labeled differently, depend-
ing on the model number.

Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.

Note:
Maintain electrical isolation
between analog input 1, digi-
tal input-outputs, switched
dc/open collector outputs and
process outputs to prevent
ground loops.

Note:
The control output common
terminal and the digital com-
mon terminal are referenced
to different voltages and
must remain isolated.

Output 2 Solid-state Relay, Form A

common

normally open

L1

K1

J1

L2

K2

T1

S1

R1

Slot A

• 0.5 A at 20 to 264V

Å (ac) maxi-

mum resistive load

• 20 VA 120/240V

Å (ac) pilot duty

• opto-isolated, without contact

suppression

• maximum off state leakage of

105 microamperes

• Output does not supply power.
• Do not use on dc loads.
See Quencharc note.

PM6 _ _ _ K-_ _ _ _ A _ _

Internal Circuitry

common

normally

open

Solid-state Relay

L2

K2

Output 3 Switched DC/Open Collector

dc +

common

X3

W3

Y3

L4

K4

T2

S2

R2

Slot B

dc - (open collector)

Switched DC
• 30 mA dc maximum supply

current

• short circuit limited to <50 mA
• 22 to 32V

Î (dc) open circuit

voltage

• Use dc- and dc+ to drive exter-

nal solid-state relay.

• DIN-A-MITE compatible
• single-pole: up to 4 in parallel

or 4 in series

• 2-pole: up to 2 in parallel or 2

in series

• 3-pole: up to 2 in series

Open Collector
• 100 mA maximum output cur-

rent sink

• 30V

Î (dc) maximum supply

voltage

• Any switched dc output can

use the common terminal.

• Use an external power supply

to control a dc load, with the
load positive to the positive
of the power supply, the load
negative to the open collector
and common to the power sup-
ply negative.

See Quencharc note.
PM6 _ _ _ _-_ _ C _ A _ _

Internal
Circuitry

dc-

dc+

Load

Switched DC

-

+

W3

Y3

Power

Supply

-

+

Internal
Circuitry

dc-

common

dc+

Open

Collector

W3

X3

Load

-

+

Output 3 Mechanical Relay, Form C

normally open

normally closed

common

L3

K3

J3

L4

K4

T2

S2

R2

Slot B

• 5 A at 240V

Å (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty at 120/240V

Å

(ac), 25 VA at 24V

Å (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
PM6 _ _ _ _-_ _ E _ A _ _

Internal
Circuitry

common

normally

open

Mechanical

Relay

L3

K3

normally

closed

J3

Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor.