beautypg.com

Proportional plus integral (pi) control, Dead band – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 63

background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

6 1

C h a p t e r 9 F e a t u r e s

In an application with one output assigned to

heating and another assigned to cooling, each will
have a separate proportional parameter. The heating
parameter takes effect when the process temperature
is lower than the set point, and the cooling param-
eter takes effect when the process temperature is
higher than the set point.

Adjust the proportional band with Heat Pro-

portional Band

[`h;Pb] or Cool Proportional Band

[`C;Pb] (Operations Page, Loop Menu).

Time

Temperature

Set Point

Proportional Band

Droop

Overshoot

Proportional plus Integral (PI) Control

The droop caused by proportional control can be cor-
rected by adding integral (reset) control. When the
system settles down, the integral value is tuned to
bring the temperature or process value closer to the
set point. Integral determines the speed of the cor-
rection, but this may increase the overshoot at start-
up or when the set point is changed. Too much inte-
gral action will make the system unstable. Integral
is cleared when the process value is outside of the
proportional band.

Adjust the integral with Time Integral

[``ti]

(Operations Page, Loop Menu).

Proportional plus Integral plus Derivative (PID)

Control

Use derivative (rate) control to minimize the over-
shoot in a PI-controlled system. Derivative (rate) ad-
justs the output based on the rate of change in the
temperature or process value. Too much derivative
(rate) will make the system sluggish.

Derivative action is active only when the process

value is within twice the proportional value from the
set point.

Adjust the derivative with Time Derivative

[``td] (Operations Page, Loop Menu).

Time

Temperature

Set Point

Reduced Overshoot

Proportional Band

Proportional Band x 2

Heating Slows

Dead Band

In a PID application the dead bands above and below
the set point can save an application’s energy and
wear by maintaining process temperature within ac-
ceptable ranges.

Proportional action ceases when the process value

is within the dead band. Integral action continues to
bring the process temperature to the set point.

Using a positive dead band value keeps the two

systems from fighting each other.

Time

Te

mperature

Positive Dead Band

Set Point

Heat Output Active

Cool Output Active

When the dead band value is zero, the heat-

ing output activates when the temperature drops be-
low the set point, and the cooling output switches on
when the temperature exceeds the set point.

Time

Te

mperature

Zero Dead Band

Set Point

Heat Output Active

Cool Output Active