Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 34
Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
3 2
•
C h a p t e r 5 O p e r a t i o n s P a g e
Display
Parameter name
Description
Set-
tings
Range
Default
Appears If
[P;Str]
{P.Str]
Profile Status
Profile Start
Select a step or profile to load.
1 to 40
0 (none)
always
[P;ACr]
{P.ACr]
Profile Status
Profile Action Request
Select what action to apply to the currently loaded
profile.
[nonE] None
[ProF] Profile Start
[PAUS] Pause
[rESU] Resume
[`End] End
[StEP] Step Start
None
always
[`StP]
[ StP]
Profile Status
Active Step
View the currently running step.
0 to 40
0 (none)
always
[S;typ]
[S.typ]
Profile Status
Active Step Type
View the currently running step type.
[UStP] Unused Step
[``ti] Time
[rAtE] Rate
[SoAH] Soak
[`W;E] Wait For Event
[W;Pr] Wait For Process
[W;bo] Wait For Both
[``JL] Jump Loop
[`End] End
Unused
Step
a profile is
active.
[tg;SP]
[tg.SP]
Profile Status
*Active Target Set Point
View or change the target set point of the current
step.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
0.0°F
or units
-18.0°C
a profile is
active.
[AC;SP]
[AC.SP]
Profile Status
Active Set Point
Display the current set point, even if the profile is
ramping.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
0.0°F
or units
-18.0°C
always
[`S;ti]
[ S.ti]
Profile Status
* Step Time Remaining
View or change the time remaining for the current
step.
Step is displayed in seconds. If the time exceeds
9,999 seconds, the display will show 9,999 and
remain there while the control continues to
decrement internally. Once the remaining time
is equal to or less than 9,999 the display will
represent the actual seconds remaining.
As an example, if a three-hour soak time is cur-
rently being monitored, the first value displayed
will be 9,999, and the display will remain at
9,999 until the remaining time is approximately
equal to 2 hours and 46 minutes. At this point
the display will track the actual seconds re-
maining.
0 to 9,999.000 seconds
0.0
always
[Ent1]
[Ent1]
[Ent2]
[Ent2]
Profile Status
*Active Event Output (1 or 2)
View or change the event output states.
[`off] Off
[``on] On
Off
always
[``JC]
[ JC]
Profile Status
Jump Count Remaining
View the jump counts remaining for the current
loop. In a profile with nested loops, this may not
indicate the actual jump counts remaining.
0 to 9,999
0
always
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.