Indication

Description

Possible Cause(s)

Corrective Action

[Li;h1] Limit High
[Li;h2]

Sensor input above high limit

set point

• Temperature is greater than limit set

point

• Limit outputs latch and require reset

• Incorrect alarm set point

• Check cause of over temperature

• Clear limit

• Establish correct limit set point

[LP;o1]
Loop Open Error

Open Loop Detect is active

and the process value did
not deviate by a user-select-
ed value in a user specified
period.

• Setting of Open Loop Detect Time

incorrect

• Setting of Open Loop Detect Devia-

tion incorrect

• Thermal loop is open

• Open Loop Detect function not re-

quired but activated

• Set correct Open Loop Detect Time for

application

• Set correct Open Loop Deviation value

for application

• Determine cause of open thermal loop:

misplaced sensors, load failure, loss of
power to load, etc.

• Deactivate Open Loop Detect feature

[LP;r1]
Loop Reversed Error

Open Loop Detect is active

and the process value is
headed in the wrong direc-
tion when the output is
activated based on devia-
tion value and user-selected
value.

• Setting of Open Loop Detect Time

incorrect

• Setting of Open Loop Detect Devia-

tion incorrect

• Output programmed for incorrect

function

• Thermocouple sensor wired in reverse

polarity

• Set correct Open Loop Detect Time for

application

• Set correct Open Loop Deviation value

for application

• Set output function correctly

• Wire thermocouple correctly, (red wire

is negative)

[`rP1] Ramping 1

Controller is ramping to new

set point

• Ramping feature is activated

• Disable ramping feature if not re-

quired

[tUN1] Autotuning 1 Controller is autotuning the

control loop

• User started the autotune function

• Digital input is set to start autotune

• Wait until autotune completes or dis-

able autotune feature

• Set digital input to function other

than autotune, if desired

No heat/cool action

Output does not activate load • Output function is incorrectly set

• Control mode is incorrectly set

• Output is incorrectly wired

• Load, power or fuse is open

• Control set point is incorrect

• Incorrect controller model for applica-

tion

• Set output function correctly

• Set control mode appropriately (Open

vs Closed Loop)

• Correct output wiring

• Correct fault in system

• Set control set point in appropriate

control mode and check source of set
point: remote, idle, profile, closed loop,
open loop

• Obtain correct controller model for ap-

plication

No Display

No display indication or LED

illumination

• Power to controller is off

• Fuse open

• Breaker tripped

• Safety interlock switch open

• Separate system limit control acti-

vated

• Wiring error

• Incorrect voltage to controller

• Turn on power

• Replace fuse

• Reset breaker

• Close interlock switch

• Reset limit

• Correct wiring issue

• Apply correct voltage, check part

number

No Serial Communi-

cation

Cannot establish serial com-

munications with the con-
troller

• Address parameter incorrect

• Incorrect protocol selected

• Baud rate incorrect

• Parity incorrect

• Wiring error

• EIA-485 converter issue

• Incorrect computer or PLC communi-

cations port

• Incorrect software setup

• Termination resistor may be required

• Set unique addresses on network

• Match protocol between devices

• Match baud rate between devices

• Match parity between devices

• Correct wiring issue

• Check settings or replace converter

• Set correct communication port

• Correct software setup to match con-

troller

• Place 120 Ω resistor across EIA-485

on last controller