C h a p t e r 6 S e t u p P a g e

Dis-

play

Parameter Name

Description

Set-

tings

Range

Default

Appears If

[FAiL]
[FAiL]

Loop
Input Error Failure

Select what the controller outputs will do
when an input error switches control to
manual mode.

[`oFF] Off, sets output power

to 0%

[bPLS] Bumpless, maintains

same output power, if it was
less than 75% and stable,
otherwise 0%

[MAn] Manual Fixed, sets

output power to Manual
Power setting

[USEr] User, sets output

power to last open-loop set
point the user entered

Off

always

[MAn]
[MAn]

Loop
Manual Power

Set the manual output power level that
will take effect if an input error failure
occurs.

Set Point Open Loop Limit

Low to Set Point Open Loop
Limit High (Setup Page)

0.0

Input Error Failure is set

to Manual Fixed.

[`L;dE]
[ L.dE]

Loop
Open Loop Detect Enable

Turn on the open-loop detect feature to
monitor a closed-loop operation for the ap-
propriate response.

[``no] No
[`YES} Yes

No

controller is equipped

with a current trans-
former input (PM6 _ _ _
_ - _T _ _ _ _ _).

[`L;dt]
[ L.dt]

Loop
Open Loop Detect Time

The Open Loop Detect Deviation value
must occur for this time period to trigger
an open-loop error.

0 to 3,600 seconds

240

Open Loop Detect Enable

is set to Yes.

[`L;dd]
[ L.dd]

Loop
Open Loop Detect Deviation

Set the value that the process must devi-
ate from the set point to trigger an open-
loop error.

-1,999.000 to 9,999.000°F or

units

-1,110.555 to 5,555.000°C

10.0°F or units

6.0°C

Open Loop Detect Enable

is set to Yes.

[``rP]
[ rP]

Loop
Ramp Action

Select when the controller's set point will
ramp to the defined end set point.

[`oFF] Off
[`Str] Startup
[StPt] Set Point Change
[both] Both

Off

always

[`r;SC]
[ r.SC]

Loop
Ramp Scale

Select the scale of the ramp rate.

[hoUr] Hours
[Min] Minutes

Minutes

Ramp Action is set to

Startup, Set Point or
Both.

[`r;rt]
[ r.rt]

Loop
Ramp Rate

Set the rate for the set point ramp. Set
the time units for the rate with the Ramp
Scale parameter.

0.0 to 9,999.000°F or units

0.0 to 5,555.000°C

1.0°F or units

1.0°C

Ramp Action is set to

Startup, Set Point or
Both.

[`L;SP]
[ L.SP]

Loop
Low Set Point

Set the low end of the set point range.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

-1,999°F or

units

-1,128°C

always

[`h;SP]
[ h.SP]

Loop
High Set Point

Set the high end of the set point range.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

9,999°F or

units

5,537°C

always

[SP;Lo]
[SP.Lo]

Loop
Set Point Low Limit Open Loop

Set the minimum value of the open-loop
set point range.

-100 to 100%

-100

always

[SP;hi]
[SP.hi]

Loop
Set Point High Limit Open Loop

Set the maximum value of the open-loop
set point range.

-100 to 100%

100

always

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.