Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 41
Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
3 9
•
C h a p t e r 6 S e t u p P a g e
Dis-
play
Parameter Name
Description
Set-
tings
Range
Default
Appears If
[otpt]
[```1] [```2] [```3] [```4]
[`Set]
[otpt] [otPt] [otpt] [otpt]
Output Menu
Output 1
Output 2
Output 3
Output 4
(check model number for output information)
[`o;ty]
[ o.ty]
Output (1 or 3)
Type
Select whether the process output will op-
erate in volts or milliamps.
[uoLt] Volts
[`MA] Milliamps
Volts
a process output (PM6 _
_ F _-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _)
[``Fn]
[ Fn]
Output (1 or 3)
Function
Select what function will drive this output.
[`oFF] Off
[hEAt] Heat
[CooL] Cool
[dUPL] Duplex
[ALM] Alarm
[`Ent] Event
[rMt] Retransmit
Heat (output 1)
Off (output 2)
a process output (PM6 _
_ F _-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _)
[`r;Sr]
[ r.Sr]
Output (1 or 3)
Retransmit Source
Select the value that will be retransmitted.
[``Ai] Analog Input
[StPt] Set Point
[CUrr] Current
Analog Input
a process output (PM6
_ _ F _-_ _ _ _ A _ _ or
PM6 _ _ _-_ _ F _ A _ _)
and Function is set to
Retransmit.
[``Fi]
[ Fi]
Output (1 or 3)
Function Instance
Select which source instance will drive the
output.
1 to 4
1
a process output (PM6 _
_ F _-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _) and
there is more than one
instance of the Function
selection.
[`S;Lo]
[ S.Lo]
Output (1 or 3)
Scale Low
Set the minimum value of the process out-
put range in electrical units.
0.00 to 20.00
0.00
a process output (PM6 _
_ F _-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _)
[`S;hi]
[ S.hi]
Output (1 or 3)
Scale High
Set the maximum value of the process out-
put range in electrical units.
0.00 to 20.00
10.00
a process output (PM6 _
_ F _-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _)
[`r;Lo]
[ r.Lo]
Output (1 or 3)
Range Low
Set the minimum value of the retransmit
value range in process units. When the
retransmit source is at this value, the
retransmit output will be at its Scale Low
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or units
-18°C
a process output (PM6
_ _ F _-_ _ _ _ A _ _ or
PM6 _ _ _-_ _ F _ A _ _)
and Function is set to
Retransmit.
[`r;hi]
[ r.hi]
Output (1 or 3)
Range High
Set the maximum value of the retransmit
value range in process units. When the
retransmit source is at this value, the re-
transmit output will be at its Scale High
value.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
9,999.0°F or
units
5,537.0°C
a process output (PM6
_ _ F _-_ _ _ _ A _ _ or
PM6 _ _ _-_ _ F _ A _ _)
and Function is set to
Retransmit.
[`o;Lo]
[ o.Lo]
Output (1 or 3)
Low Power Scale
Set the minimum value of the output
range.
0.0 to 100.0%
0.0
a process output (PM6 _ _
F
_-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _) and
Function is set to Heat
or Cool.
[`o;hi]
[ o.hi]
Output (1 or 3)
High Power Scale
Set the maximum value of the output
range.
0.0 to 100.0%
100.0
a process output (PM6 _ _
F
_-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _) and
Function is set to Heat
or Cool.
[`o;CA]
[ o.CA]
Output (1 or 3)
Calibration Offset
Set an offset value for a process output.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
0.0°F or units
0.0°C
a process output (PM6 _ _
F
_-_ _ _ _ A _ _ or PM6
_ _ _-_ _ F _ A _ _)
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.