Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
4 2
•
C h a p t e r 6 S e t u p P a g e
Dis-
play
Parameter Name
Description
Set-
tings
Range
Default
Appears If
[`C;Si]
[ C.Si]
Current
Source Output Instance
Select which output instance the current
transformer will monitor.
1 to 6
1 (if not pro-
cess)
2 (otherwise)
always
[`FUn]
[`Set]
Function Key Menu
[`Leu]
[ LEv]
Function Key
Level
Select what state the Function Key will be
in at startup.
Pressing the Function Key will toggle the
selected action.
[high] High
[Low] Low
High
always
[``Fn]
[ Fn]
Function Key
Digital Input Function
Program the EZ Key to trigger an action.
Functions respond to a level state change
or an edge level change.
[none] None
[idLE] Idle Set Point Enable
(level)
[tUnE] Tune (edge)
[ALM] Alarm Reset (edge)
[`SiL] Silence Alarms (edge)
[MAn] Manual/Auto Mode
(level)
[`oFF] Control Outputs Off
(level)
[`r;En] Remote Set Point En-
able (level)
[P;LoC] Lock Keypad (level)
[`F;AL] Force Alarm (level)
[`t;dA] TRU-TUNE+
®
Dis-
able (level)
[`AoF] Alarm Outputs &
Control Loop Off (level)
[USr;r] Restore User Settings
(edge)
[P;diS] Profile Disable (level)
[P;hoL] Profile Hold/Resume
(level)
[ProF] Profile Start Number
(edge)
[P;StS] Profile Start/Stop
(level)
[LMr] Limit Reset (edge)
None
always, but only the
available features can be
selected.
[``Fi]
[ Fi]
Function Key
Instance
Select which instance the EZ Key will af-
fect. If only one instance is available, any
selection will affect it.
0 All Instances (except Pro-
file)
(For example, if Digital Func-
tion is set to Silence Alarms
and Function Instance is set
to 0, then the digital input
would silence all alarms.)
1 to 4
0
there is more than one
instance of the Digital
Input Function selec-
tion.
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which units will be displayed.
[```F] °F
[```C] °C
°F
always
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the applied ac line
power source.
[``50] 50 Hz
[``60] 60 Hz
60 Hz
always
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.