Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 53
Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
5 1
•
C h a p t e r 8 F a c t o r y P a g e
Dis-
play
Parameter Name
Description
Set-
tings
Range
Default
Appears If
[rLoC]
[rLoC]
Lockout Menu
Read Lockout Security
Set the read security clearance
level. The user can access the se-
lected level and all lower levels.
If the Set Lockout Security level
is higher than the Read Lockout
Security, the Read Lockout Secu-
rity level takes priority.
1 to 5
1 Home Page
2 Operations Page*
3 Profiling Page*
4 Setup Page and Diagnostics Menu
5 Lock, Calibration and Custom menus
*You can change the security level of the
Operations and Profiling pages with
Lock Operations Page and Lock Profil-
ing Page.
5
always
[SLoC]
[SLoC]
Lockout Menu
Set Lockout Security
Set the write security clearance
level. The user can access the se-
lected level and all lower levels.
If the Set Lockout Security level
is higher than the Read Lockout
Security, the Read Lockout Secu-
rity level takes priority.
0 to 5
0 No changes allowed, except to
[SLoC]
1 Home Page
2 Operations Page*
3 Profiling Page*
4 Setup Page and Diagnostics Menu
5 Lock, Calibration and Custom menus
*You can change the security level of the
Operations and Profiling pages with
Lock Operations Page and Lock Profil-
ing Page.
5
always
[diAg]
[FCty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this controller's part
number.
always
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this controller's firmware
revision number.
always
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build
Display the firmware build num-
ber.
0 to 2,147,483,647
always
[``Sn]
[ Sn]
Diagnostics Menu
Serial Number
Display the serial number.
0 to 2,147,483,647
always
[dAtE]
[dAtE]
Diagnostics Menu
Date of Manufacture
Display the date code.
0 to 2,147,483,647
always
[USr;r]
[USr.r]
Diagnostics Menu
User Restore Set
Replace all of this controller's set-
tings with another set.
[none] None
[SEt1] User Set 1
[SEt2] User Set 2
[FCty] Factory Default
None
always
[USr;S]
[USr.S]
Diagnostics Menu
User Save Set
Save all of this controller's set-
tings to the selected set.
[none] None
[SEt1] User Set 1
[SEt2] User Set 2
None
always
[iP;A1]
[iP.A1]
Diagnostics Menu
IP Actual Address Part 1
Display the first part of this
controller's IP address.
0 to 255
None
the controller in-
cludes EtherNet/
IP (PM6 _ _ _ _-
3AA
_ A _ _).
[iP;A2]
[iP.A2]
Diagnostics Menu
IP Actual Address Part 2
Display the second part of this
controller's IP address.
0 to 255
None
the controller in-
cludes EtherNet/
IP (PM6 _ _ _ _-
3AA
_ A _ _).
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with another interface.
If there is only one instance of a menu, no submenus will appear.