Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 33
Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
3 1
•
C h a p t e r 5 O p e r a t i o n s P a g e
Display
Parameter name
Description
Set-
tings
Range
Default
Appears If
[``dB]
[ db]
Loop
Dead Band
Set the offset to the proportional band. With a
negative value, both heating and cooling outputs
are active when the process value is near the set
point. A positive value keeps heating and cooling
outputs from fighting each other.
-1,000.0 to 1,000.0°F or units
-556 to 556°C
0.0
Heat Algorithm
and Cool Algo-
rithm (Setup
Page) are set to
PID or On-Off.
[`o;SP]
[ o.SP]
Loop
Open Loop Set Point
Set a fixed level of output power when in manual
(open-loop) mode.
-100 to 100% (heat and cool)
0 to 100% (heat only)
-100 to 0% (cool only)
0.0
always
[ ALM]
[```1] [```2] [```3] [```4]
[oPEr]
[ALM] [ALM] [ALM] [ALM]
Alarm Menu
Alarm 1
Alarm 2
Alarm 3
Alarm 4
[`A;Lo]
[ A.Lo]
Alarm (1 to 4)
Low Set Point
If Alarm Type (Setup Page, Alarm Menu) is set to:
process
- set the process value that will trigger a
low alarm.
deviation
- set the span of units from the closed
loop set point that will trigger a low alarm.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
32.0°F
or units
0.0°C
Alarm Sides
(Setup Page) is
not set to High.
[`A;hi]
[ A.hi]
Alarm (1 to 4)
High Set Point
If Alarm Type (Setup Page, Alarm Menu) is set to:
process
- set the process value that will trigger a
high alarm.
deviation
- set the span of units from the closed
loop set point that will trigger a high alarm.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
300.0°F
or units
150.0°C
Alarm Sides
(Setup Page) is
not set to Low.
[CUrr]
[oPEr]
Current Menu
(menu appears if PM6 _ _ _-_ T _ _ A _ _)
Note: To use the current sensing feature, Time Base (Setup Page, Output
Menu) must be set to 0.7 seconds or more.
[`C;hi]
[ C.hi]
Current
High Set Point
Set the current value that will trigger a high
heater error state.
-1,999.000 to 9,999.000
50.0
Current Sides
(Setup Page) is
set to High or
Both.
[`C;Lo]
[ C.Lo]
Current
Low Set Point
Set the current value that will trigger a low
heater error state.
-1,999.000 to 9,999.000
0.0
Current Sides
(Setup Page) is
set to Low or
Both.
[`CU;r]
[ CU.r]
Current
Read
View the most recent current value monitored by
the current transformer.
-1,999.000 to 9,999.000
0
always
[`C;Er]
[ C.Er]
Current
Error
View the cause of the most recent load fault.
[nonE] None
[Shrt] Shorted
[open] Open
None
always
[`h;Er]
[ h.Er]
Current
Heater Error
View the cause of the most recent load fault moni-
tored by the current transformer.
[nonE] None
[high] High
[Low] Low
None
always
[P;Sta]
[oPEr]
Profile Status Menu
(menu appears if PM6 R _ _ _-_ _ _ _ A _ _)
* Some parameters in the Profile Status Menu can be changed for the
currently running profile, but should only be changed by knowledgeable
personnel and with caution. Changing parameters via the Profile Status
Menu will not change the stored profile but will have an immediate im-
pact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running profile.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.