Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

3 1

C h a p t e r 5 O p e r a t i o n s P a g e

Display

Parameter name

Description

Set-

tings

Range

Default

Appears If

[``dB]
[ db]

Loop
Dead Band

Set the offset to the proportional band. With a
negative value, both heating and cooling outputs
are active when the process value is near the set
point. A positive value keeps heating and cooling
outputs from fighting each other.

-1,000.0 to 1,000.0°F or units

-556 to 556°C

0.0

Heat Algorithm

and Cool Algo-
rithm (Setup
Page) are set to
PID or On-Off.

[`o;SP]
[ o.SP]

Loop
Open Loop Set Point

Set a fixed level of output power when in manual
(open-loop) mode.

-100 to 100% (heat and cool)

0 to 100% (heat only)

-100 to 0% (cool only)

0.0

always

[ ALM]

[```1] [```2] [```3] [```4]

[oPEr]

[ALM] [ALM] [ALM] [ALM]

Alarm Menu

Alarm 1

Alarm 2

Alarm 3

Alarm 4

[`A;Lo]
[ A.Lo]

Alarm (1 to 4)
Low Set Point

If Alarm Type (Setup Page, Alarm Menu) is set to:

process

- set the process value that will trigger a

low alarm.

deviation

- set the span of units from the closed

loop set point that will trigger a low alarm.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

32.0°F

or units

0.0°C

Alarm Sides

(Setup Page) is
not set to High.

[`A;hi]
[ A.hi]

Alarm (1 to 4)
High Set Point

If Alarm Type (Setup Page, Alarm Menu) is set to:

process

- set the process value that will trigger a

high alarm.

deviation

- set the span of units from the closed

loop set point that will trigger a high alarm.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

300.0°F

or units

150.0°C

Alarm Sides

(Setup Page) is
not set to Low.

[CUrr]
[oPEr]
Current Menu

(menu appears if PM6 _ _ _-_ T _ _ A _ _)

Note: To use the current sensing feature, Time Base (Setup Page, Output
Menu) must be set to 0.7 seconds or more.

[`C;hi]
[ C.hi]

Current
High Set Point

Set the current value that will trigger a high
heater error state.

-1,999.000 to 9,999.000

50.0

Current Sides

(Setup Page) is
set to High or
Both.

[`C;Lo]
[ C.Lo]

Current
Low Set Point

Set the current value that will trigger a low
heater error state.

-1,999.000 to 9,999.000

0.0

Current Sides

(Setup Page) is
set to Low or
Both.

[`CU;r]
[ CU.r]

Current
Read

View the most recent current value monitored by
the current transformer.

-1,999.000 to 9,999.000

0

always

[`C;Er]
[ C.Er]

Current
Error

View the cause of the most recent load fault.

[nonE] None
[Shrt] Shorted
[open] Open

None

always

[`h;Er]
[ h.Er]

Current
Heater Error

View the cause of the most recent load fault moni-
tored by the current transformer.

[nonE] None
[high] High
[Low] Low

None

always

[P;Sta]
[oPEr]
Profile Status Menu

(menu appears if PM6 R _ _ _-_ _ _ _ A _ _)

* Some parameters in the Profile Status Menu can be changed for the

currently running profile, but should only be changed by knowledgeable
personnel and with caution. Changing parameters via the Profile Status
Menu will not change the stored profile but will have an immediate im-
pact on the profile that is running.

Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running profile.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.