Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.

Note:
Maximum wire size termina-
tion and torque rating:
• 0.0507 to 3.30 mm2 (30 to
12 AWG) single-wire termi-
nation or two 1.31 mm2 (16
AWG)
• 0.8 Nm (7.0 lb.-in.) torque

Note:
Adjacent terminals may be
labeled differently, depend-
ing on the model number.

Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.

Note:
Maintain electrical isolation
between analog input 1, digi-
tal input-outputs, switched
dc/open collector outputs and
process outputs to prevent
ground loops.

Note:
The control output common
terminal and the digital com-
mon terminal are referenced
to different voltages and
must remain isolated.

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

1 6

C h a p t e r 2 I n s t a l l a n d W i r e

Input 2 Current Transformer

L3

K3

J3

L4

K4

T2

S2

R2

Slot B

• Input range is 0 to 50 mA.
• current transformer part number: 16-0246
• 100 Ω input impedance
• response time: 1 second maximum
• accuracy +/-1 mA typical

PM6 _ _ _ _-_ T _ _ A _ _