Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual
Page 42

Wa t l o w E Z - Z O N E
®
P M I n t e g r a t e d C o n t r o l l e r
•
4 0
•
C h a p t e r 6 S e t u p P a g e
Dis-
play
Parameter Name
Description
Set-
tings
Range
Default
Appears If
 [``Fn]
[ Fn]
Output (1 to 4) 
 Function
Select what function will drive this output.
[`oFF] Off 
[hEAt] Heat 
[CooL] Cool 
[ALM] Alarm 
[`Ent] Event 
[LiM] Limit (outputs 3 & 4)
Heat
Alarm
Off (outputs 3
& 4)
a time-proportioned out-
put (solid-state relay, 
switched dc or mechani-
cal relay)
 [``Fi]
[ Fi]
Output (1 to 4) 
 Function Instance
Select which source instance will drive the 
output.
1 to 4
1
a time-proportioned out-
put (solid-state relay, 
switched dc or mechani-
cal relay), and there is 
more than one instance 
of the Function selec-
tion. 
 [`o;Ct] 
[ o.Ct]
Output (1 to 4) 
 Control
Set the output control type. This param-
eter is only used with PID control, but can 
be set anytime.
[`Ftb] Fixed Time Base 
[`utb] Variable Time Base 
Fixed Time
Base
a time-proportioned out-
put (solid-state relay, 
switched dc or mechani-
cal relay).
If output 1 is a universal
process output, output 
2 cannot function as 
a variable-time-base 
output. If output 3 is 
a universal process 
output, output 4 cannot 
function as a variable-
time-base output.
 [`o;tb]
[ o.tb]
Output (1 to 4) 
 Time Base
Set the time base for fixed-time-base con-
trol.
0.1 to 60.0 seconds (solid-
state relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or no-arc power 
control)
0.1 sec. [SSR &
sw dc]
20.0 sec.
[mech, relay, 
no-arc]
a time-proportioned
output (solid-state 
relay, switched dc or 
mechanical relay) and 
Control is set to Fixed 
Time Base. 
 [`o;Lo]
[ o.Lo]
Output (1 to 4) 
 Low Power Scale
The power output will never be less than 
the value specified and will represent the 
value at which output scaling begins.
0.0 to 100.0%
0.0%
a time-proportioned out-
put (solid-state relay, 
switched dc or mechani-
cal relay) and Source is 
set to Heat or Cool.
 [`o;hi]
[ o.hi]
Output (1 to 4) 
 High Power Scale
The power output will never be greater 
than the value specified and will represent 
the value at which output scaling stops.
0.0 to 100.0%
100.0%
a time-proportioned out-
put (solid-state relay, 
switched dc or mechani-
cal relay) and Source is 
set to Heat or Cool.
[Alm]
[```1] [```2] [```3] [```4]
[`Set]
[Alm] [Alm] [Alm] [Alm]
Alarm Menu
Alarm 1
Alarm 2
Alarm 3
Alarm 4
 [`A;ty]
[ A.ty]
Alarm (1 to 4) 
 Type
Select how the alarm will or will not track 
the set point.
[`oFF] Off 
[PR;AL] Process Alarm 
[dE;AL] Deviation Alarm 
Off
always
 [`sr;a]
[ Sr.A]
Alarm (1 to 4) 
 Source
Select what will trigger this alarm.
[``Ai] Analog Input 
[PWr] Power (process only)
[CUrr] Current (process only)
Analog Input
always
 [`is;a]
[ iS.A]
Alarm (1 to 4) 
 Source Instance
If Alarm Source is set to input, select 
which input to use.
1 or 2
1
there is more than one
instance of the Source 
selection.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.