beautypg.com

Electrical data – Trane Genius PKG-PRC007-EN User Manual

Page 44

background image

PKG-PRC007-EN

44

Table ED-8 — Genius – Electrical Features - SAVE100

Nominal Operation Values

Compressor 1

Compressor 2

Fan Motor

Consumption

Current

Fan

Voltage

KW

CNO

KW

CNO

KW

CNO

KW

A

220V

14.10

14.10

4.14

32.34

STD

380V

4.17

8.16

4.17

8.16

1.22

2.39

9.56

18.71

440V

7.05

7.05

2.07

16.17

220V

14.10

14.10

5.53

33.73

Option 1

380V

4.17

8.16

4.17

8.16

1.64

3.19

9.98

19.51

440V

7.05

7.05

2.76

16.86

220V

14.10

14.10

7.32

35.52

Option 2

380V

4.17

8.16

4.17

8.16

2.23

4.23

10.57

20.55

440V

7.05

7.05

3.66

17.76

Plenum Box

220V

14.10

14.10

1.80

30.00

Option

380V

4.17

8.16

4.17

8.16

0.45

1.04

8.79

17.36

440V

7.05

7.05

0.90

15.00

Maximum operation values

Compressor 1

Compressor 2

Fan Motor

Current

Fan

Voltage

CMO

CMO

CMO

A

220V

19.80

19.80

5.18

44.78

STD

380V

11.46

11.46

2.99

25.91

440V

9.90

9.90

2.59

22.39

220V

19.80

19.80

6.91

46.51

Option 1

380V

11.46

11.46

3.99

26.91

440V

9.90

9.90

3.46

23.26

220V

19.80

19.80

9.15

48.75

Option 2

380V

11.46

11.46

5.28

28.20

440V

9.90

9.90

4.58

24.38

Plenum Box

220V

19.80

19.80

2.25

41.85

Option

380V

11.46

11.46

1.30

24.22

440V

9.90

9.90

1.13

20.93

Start-up values

Compressor 1

Compressor 2

Fan Motor

Fan

Voltage

LRA

LRA

LRA

220V

128.00

128.00

30.92

STD

380V

74.11

74.11

17.85

440V

64.00

64.00

15.46

220V

128.00

128.00

48.36

Option 1

380V

74.11

74.11

27.92

440V

64.00

64.00

24.18

220V

128.00

128.00

60.45

Option 2

380V

74.11

74.11

34.90

440V

64.00

64.00

30.23

Plenum Box

220V

128.00

128.00

11.25

Option

380V

74.11

74.11

6.50

440V

64.00

64.00

5.63

Electrical
Data

To know which ventilation option should be used, consult the behavior of the

ventilation options.

CNO = Nominal operation current (A).

CMO = Maximum operation current.

LRA = Locked rotor amps.

STD Option - evaporator fan motor -1.5 CV.

Option 1 - evaporator fan motor -2 CV.

Option 2 - evaporator fan motor -3 CV.

Plenum box option - evaporator fan motor -0.5 CV.

Size the electrical wiring using the maximum operation currents.