No flow delay 005 gpm 3 minutes – Toro 12 User Manual

Page 57

background image

51

HIGH FLOW DELAY
050 GPM 3 Minutes

NO FLOW THRESHOLD
005 GPM 3 Minutes

3.

Turn the Upper Line knob (right) to select High Flow Delay.

1.

Turn the Upper Line knob (right) to select No Flow Threshold.

NO FLOW DELAY
005 GPM 3 Minutes

3.

Turn the Upper Line knob (right) to select No Flow Delay.

4.

Turn the Lower Line knob to adjust the delay minutes (1–6).

4.

Turn the Lower Line knob to adjust the delay period (1–6 minutes).

Setting the No Flow Threshold

Note: To prevent a false alert response, the No Flow threshold should be
set 10–15%

lower than the expected flow in any program configuration.

2.

The default threshold will be displayed. To adjust, turn the Lower

Line knob. The value is adjustable from Off –30 in one-GPM

increments, or 30–995 in five-GPM increments.