7. Quick heating

control

Operation flow and applicable data, etc.

This function quickens the starting of heating opera-
tion when indoor/outdoor temperature is low.
(Available only in heating operation)

When indoor temperature is low, this function stores
the heat by heating winding depended on the outdoor
temperature and then it enables the hot air blowing
out quickly.

Description

When the following conditions are
satisfied, winding is heated by output
varied by the outdoor heat exchanger
temperature.

Condition 1 :

The previous operation was heating.

Condition 2 :

2 hours passed after operation stop.

Condition 3 :

The room temperature is 20°C or lower.

The indoor temperature sensor detects
the room temperature.
If the detected room temperature is 20°C
or lower, the outdoor heat exchanger
temperature sensor detects the outdoor
heat exchanger temperature. As shown in
the left figure, winding of the compressor
is heated for each division of the tempera-
ture ( for each outdoor temperature) and
the heat is stored.

8. Defrost control

(Only in heating
operation)

(This function removes frost adhered to the outdoor
heat exchanger.)

The temperature sensor of the outdoor heat ex-
changer (Te sensor) judges the frosting status of the
outdoor heat exchanger and the defrost operation is
performed with 4-way valve reverse defrost system.

The necessity of defrost operation is
detected by the outdoor heat exchanger
temperature. The conditions to detect the
necessity of defrost operation differ in A,
B, or C zone each. (Table 1)

• Defrost operation in A to C zones

1) Stop operation of the compressor for

20 seconds.

2) Invert (ON) 4-way valve 10 seconds

after stop of the compressor.

3) The outdoor fan stops at the same time

when the compressor stops.

4) When temperature of the indoor heat

exchanger becomes 38°C or lower,
stop the indoor fan.

• Returning conditions from defrost

operation to heating operation

1) Temperature of outdoor heat exchanger

rises to +8°C or higher.

2) Temperature of outdoor heat exchanger

is kept at +5°C or higher for 80 seconds.

3) Defrost operation continues for

15 minutes.


1) Stop operation of the compressor for

approx. 50 seconds.

2) Invert (OFF) 4-way valve approx. 40

seconds after stop of the compressor.

3) The outdoor fan starts rotating at the

same time when the compressor starts.

Table 1

* The minimum value of Te sensor 10 to 15 minutes

after start of operation is stored in memory as Te0.

20˚C

–1˚C
–3˚C

–6˚C
–8˚C

OFF

Heating output for winding

20W or equivalent

20W or equivalent

Winding is not heated.

Indoor temper

ature

Outdoor heat e

xchanger

temper

ature

The previous operation was heating and

2 hours passed after the operation had stopped.

In case of operation stop

YES

NO

–5˚C

0’

10’ 15’

27’40”

34’

–7˚C

–20˚C

Operation time
(Minute)

Start of heating operation

*

Outdoor heat e

xchanger temper

ature

C zone

A zone

B zone

A zone

B zone

C zone

When Te0 - TE

2.5 continued for 2 minutes in A zone,

defrost operation starts.

When the operation continued for 2 minutes in B zone,
defrost operation starts.

When Te0 - TE

3 continued for 2 minutes in C zone,

defrost operation starts.