beautypg.com

Telex Integrated Signal Processor ISP-100 User Manual

Page 119

background image

8-49

Processing Components - Limiter

one. The two quantities are then compared and the larger is
returned as the signal level.

When the Crest Factor Sensitivity is set to 0.00 the ISP-100
limiter operates as a traditional limiter responding to average
signal levels; when the Crest Factor Sensitivity is set to 1.00 the
ISP-100 limiter operates as a traditional limiter responding to
peak signal levels. Values in-between represent various hybrids
of the two. If the limiter is to ignore peaks and respond only to
average levels, then the Crest Factor Sensitivity may be set near
zero. If the limiter is to respond only to peaks, then the Crest
Factor Sensitivity may be set near one.

Good results may be obtained by following these steps:

1. Set the Crest Factor Sensitivity to 0.00. This will cause the
ISP-100 limiter to behave like a traditional limiter responding
to average signal levels.

2. Set all of the other limiter controls as appropriate for the
signal being limited, just as they would be set in a traditional
limiter.

3. Adjust the Crest Factor Sensitivity control so that the limiter
responds appropriately to short signal peaks. If it were
possible to know, in advance, what the crest factor of the
input signal was going to be, then the Crest Factor Sensitivity
control would ideally be set to 1/(the crest factor of the input
signal).

Since this quantity is not generally known, it is best to
experiment until satisfactory results are obtained.

Metering
The limiter meter shows the attenuation applied to the signal
passing through the limiter at any given moment in time. When
the signal is being limited the meter indicates negative values
(gain less than 1.0). When the signal is

not being limited the

meter indicates 0 dB (gain of 1.0). Meter values are raw, no
averaging or ballistics are applied.

Notes on Operation of the Limiter:

Bypass
Bypassing a limiter causes the signal to pass through unaltered.

Overshoot
The limiter algorithm used in the ISP-100 allows for a small
amount of overshoot on transients, regardless of the settings of
the Detection Window and Crest Factor Sensitivity controls. The
amount of overshoot is somewhat dependent upon the setting of
the Threshold control; the lower the threshold the greater the
overshoot. This represents normal operation for the limiter.