INSTALLING OPTIONAL ACCESSORIES
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
S 164201603 Rev 2 www.powerware.com
6-5
9.
Contact your Eaton service representative for verification and testing of the RIM
and its connections prior to making connections with J1 through J4 (see
Table 6‐1 and Drawing 164201603-12 on page A-63).
You can order interface cables separately for connecting to the 15‐Pin D‐Sub
Connectors.
Table 6‐1. J1 through J4 Interface Connectors
Status
J1 through J4
Description
UPS
AVAILABLE
Pins 1 and 12
Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode or
ready to supply the load.
UPS OFFLINE
Pins 3 and 13
Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode or
ready to supply the load.
BATTERY
WEAK
Pins 5 and 14
Contacts are closed when approximately two minutes of battery
time is remaining, before the critical load is lost.
UTILITY
FAILURE
Pins 6 and 15
Contacts are closed when Utility Failure is detected.