See appendix a, table s, Table s – Powerware 9390 UPS 100160 kVA User Manual
Page 176

POWER WIRING INSTALLATION NOTES
071608
C
18 of 23
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
S 164201603 Rev 2 www.powerware.com
A-28
29.
See Drawing 164201603-7 for UPM terminal locations and Table K, Table L, or Table M for
termination requirements.
30.
Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer
. Contact service to schedule a date.
31.
For parallel system circuit breaker ratings, see appropriate information in Table R.
32.
For parallel system ratings, see the appropriate information in Table S through Table V.
Table R. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
Circuit Breaker Ratings
UPM
Model
Configuration
Output Voltage
208V/220V
380V/400V/415V
480V
MOB
MIS
MBP
MOB
MIS
MBP
MOB
MIS
MBP
9390-40/20
9390-40/30
9390-40/40
9390-80/40
1+1
150
150
150
90
90
90
70
70
70
2+0 and 2+1
150
300
300
90
200
200
70
150
150
3+0 and 3+1
150
450
450
90
300
300
70
200
200
4+0
150
600
600
90
400
400
70
250
250
9390-80/50
1+1
200
200
200
110
110
110
80
80
80
2+0 and 2+1
200
350
350
110
225
225
80
175
175
3+0 and 3+1
200
600
600
110
350
350
80
250
250
4+0
200
700
700
110
450
450
80
350
350
9390-80/60
1+1
225
225
225
125
125
125
100
100
100
2+0 and 2+1
225
500
500
125
250
250
100
200
200
3+0 and 3+1
225
700
700
125
400
400
100
300
300
4+0
225
1000
1000
125
500
500
100
400
400
9390-80/80
1+1
300
300
300
150
150
150
125
125
125
2+0 and 2+1
300
600
600
150
300
300
125
250
250
3+0 and 3+1
300
1000
1000
150
450
450
125
400
400
4+0
300
1200
1200
150
600
600
125
500
500