POWER WIRING INSTALLATION NOTES
110106
B
NOTE Customer ground can be run in any conduit listed in Table N.
7 of 23
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
S 164201603 Rev 2 www.powerware.com
A-17
10.
Terminals are UL and CSA rated at 90°C. Refer to Table K through Table M for power cable
terminations, and Table N for conduit requirements. Drawing 164201603-7 shows the
location of the power cable terminals inside the UPS cabinet.
Table K. UPS Cabinet Power Cable Terminations for the Powerware 9390-80/40,
9390-80/50, 9390-80/60, and 9390-80/80 (208V/220V Input and 208V/220V Output)
Terminal Function
Terminal Function
Size of Pressure
Termination
Tightening
Torque
Nm (lb in)
Type
Screw
AC Input to UPS Rectifier
and Bypass
(Single Input)
E6
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E7
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E8
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
AC Input to UPS Rectifier
(Dual Input)
E1
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E2
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E3
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
AC Input To Bypass
(Dual Input)
E6
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E7
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E8
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
Single‐Feed To Dual‐Feed
Remove Jumpers between
Rectifier Input Terminals
and Bypass Input
Terminals
Rectifier
Phase A
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase A
N/A
22.6 (200)
M10 Hex Bolt
Rectifier
Phase B
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase B
N/A
22.6 (200)
M10 Hex Bolt
Rectifier
Phase C
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase C
N/A
22.6 (200)
M10 Hex Bolt
AC Output to
Critical Load
E9
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E10
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
E11
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16 in. Hex
DC Input from
Battery to UPS
E4
Positive
1 - #6-350 kcmil
31.1 (275)
5/16 in. Hex
E5
Negative
1 - #6-350 kcmil
31.1 (275)
5/16 in. Hex
Input and Output Neutral
E12
Neutral
8 - #2-600 kcmil
56.5 (500)
1/2 in. Hex
Customer Ground
Ground
Ground
8 - #14-1/0
5.6 (50)
Slotted