Powerware 9390 UPS 100160 kVA User Manual
Page 169

POWER WIRING INSTALLATION NOTES
110106
B
11 of 23
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
S 164201603 Rev 2 www.powerware.com
A-21
Table N. Power Cable Conduit Requirements (Cont'd)
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size (inches)
Number of
Conduits
Powerware
9390-40/40
and
9390-80/40
208/220
AC
AC Input to UPS
(A, B, C, Gnd)
4
2‐1/2
1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2‐1/2
1
Output
(A, B, C, Neut, Gnd)
5
2‐1/2
1
DC
Battery
(Positive), (Negative), Gnd
3
1
1
Powerware
9390-40/40
and
9390-80/40
480
AC
AC Input to UPS
(A, B, C, Gnd)
4
1‐1/4
1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1‐1/4
1
Output
(A, B, C, Neut, Gnd)
5
1‐1/4
1
DC
Battery
(Positive), (Negative), Gnd
3
1
1
Powerware
9390-80/50
208/220
AC
AC Input to UPS
(A, B, C, Gnd)
4
2‐1/2
1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2‐1/2
1
Output
(A, B, C, Neut, Gnd)
5
2‐1/2
1
DC
Battery
(Positive), (Negative), Gnd
3
1‐1/2
1
Powerware
9390-80/50
480
AC
AC Input to UPS
(A, B, C, Gnd)
4
1‐1/2
1
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1‐1/2
1
Output
(A, B, C, Neut, Gnd)
5
1‐1/2
1
DC
Battery
(Positive), (Negative), Gnd
3
1‐1/2
1