OPTIONAL REMOTE EMERGENCY
POWER‐OFF
071608
B
164201603-10
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
NOTE 1. Conduit and wiring between the
Remote Emergency Power‐off (REPO)
and the UPS to be supplied by the
customer.
2. Maximum distance between the
Remote EPO and the UPS not to exceed
500 feet.
3. Maximum wire size #14 AWG.
Minimum wire size #22 AWG.
Dimensions are in millimeters [inches]
NOTE Interface wiring and conduit between the REPO switch
and the UPS are to be supplied by the customer.