POWER WIRING INSTALLATION NOTES
071608
C
15 of 23
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS (20–80 kVA) Installation and Operation Manual
S 164201603 Rev 2 www.powerware.com
A-25
14.
External overcurrent protection is not provided by this product, but is required by codes.
Refer to Table E through Table J for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the user.
15.
Table O lists the maximum rating for input circuit breakers. When wiring a single‐feed
input, the rating requirements for the input circuit breakers are superceded by the ratings
listed in Table P.
Table O. Maximum Input Circuit Breaker Ratings
UPS Model
Input Voltage Rating
% Rating
208V/220V
380V
400V
415V
480V
Powerware 9390-40/20
80%
90A
50A
50A
45A
45A
100%
70A
40A
40A
35A
35A
Powerware 9390-40/30
80%
125A
70A
70A
60A
60A
100%
100A
60A
60A
50A
45A
Powerware 9390-40/40
Powerware 9390-80/40
80%
175A
90A
90A
80A
70A
100%
150A
80A
80A
70A
60A
Powerware 9390-80/50
80%
225A
110A
110A
100A
100A
100%
175A
90A
90A
90A
80A
Powerware 9390-80/60
80%
250A
150A
125A
125A
125A
100%
200A
110A
110A
100A
90A
Powerware 9390-80/80
80%
350A
175A
175A
175A
150A
100%
300A
150A
150A
150A
125A
C
A
U
T
I
O
N
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table O
in accordance with the National Electrical Code, ANSI/NFPA 70.
16.
Source protection for the AC input to bypass should be treated as if supplying an 80 kVA
three‐phase transformer, to allow for inrush current if an IDC with a transformer is installed.
Bypass input wiring and bypass input breaker rating should be treated as if supplying an
80 kVA load, regardless of the rating of the UPS.
17.
The line‐to‐line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table E through Table J.
The recommended line‐to‐line load unbalance is 50% or less.