GENERAL COMMUNICATOR OPTIONS

COMMUNICATOR ENABLE

✦ The factory setting for the Control Panel disables

the communicator. If the system is going to be
a non-monitored, local alarm only, leave the
communicator disabled.

STEP #107

If the system is going to be monitored by a

Central Station, enable the communicator with
this programming step.

2-WAY AUDIO

✦ When the Model VB-2 voice module is installed,

the communicator can provide 2-way audio
capability.

✦ The audio module can be programmed for

listen-only, 2-way manual operation (using a
pushbutton telephone at the Central Station), and
2-way full duplex hands free operation.

✦ Refer to the VB-2 installation instructions for

details on operating the audio module.

NOTE: The Model VB-2 digital voice response

module must be installed for this option to
function.

✦ The factory setting for the VB-2 audio module is OFF.

STEP #76

The audio module can be set for (1) listen-only, (2)

2-way manual, (3) 2-way full duplex using this step.

NOTE: For safety, 2-way audio will not activate if

the system is disarmed with the duress code.

NOTE:Units programmed for two-way duplex can

still be controlled manually by pressing the “1” or
“3” key. In addition, the Central Station can return
the unit to two-way duplex by pressing the “8” key.

VOICE RESPONSE

✦ The Control Panel can be programmed to allow

the keypad(s) speaker to play audio produced by
the VB-2 digital voice response module.

✦ This selection can also be used when a remote

speaker is connected to the Control Panel.

✦ The factory setting is to disable the keypad(s)

speaker from playing voice module audio.

STEP #78

The Control Panel can be programmed to enable

voice module audio using this step.

NOTE: Turning voice response OFF with this

programming step will only effect the audio produced
by the voice module. It will not stop the keypad(s)
speaker from sounding local sirens and tones.

NOTE: A Model VB-2 digital voice response module

must be installed for this option to function.

REMOTE LOCKOUT

✦ The factory setting for the communicator allows

remote connection to the Control Panel with
Linear's RA-2400 Remote Access Software and
a modem (unlocked).

STEP #100

The Control Panel can be programmed to not

answer incoming calls, thereby, not allowing
remote access (locked) using this step.

PROGRAMMING STEP #107

ENTERS STEP NUMBER

0 FOR COMMUNICATOR OFF
1 FOR COMMUNICATOR ON

STORES VALUE - 1 BING

PROGRAMMING STEP #76

ENTERS STEP NUMBER
0 FOR NO AUDIO MONITORING
1 FOR LISTEN-ONLY
2 FOR 2-WAY MANUAL
3 FOR 2-WAY FULL DUPLEX
STORES VALUE - 1 BING

PROGRAMMING STEP #78

ENTERS STEP NUMBER

0 FOR NO VOICE RESPONSE

E

1 FOR VOICE RESPONSE

STORES VALUE - 1 BING

PROGRAMMING STEP #100

ENTERS STEP NUMBER

0 FOR UNLOCK
1 FOR LOCK

STORES VALUE - 1 BING