Schneider Electric 66123 User Manual
Page 96

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 96/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
11.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)
SNMP traps are sent when alarms appears and desappears.
Level : 1:informational , 2:major, 3:critical
MIB TRAP
Trap #
niveau
-upsmgBatteryFault (Nota1)
Trap 1
Level 3
-upsmgBatteryOK (Nota1)
Trap 2
Level 1
-upsmgAtLowBattery (Nota1)
Trap 5
Level 3
-upsmgFromLowBattery (Nota1)
Trap 6
Level 1
-upsmgChargerFault (Nota1)
Trap 7
Level 3
-upsmgChargerOK (Nota1)
Trap 8
Level 1
-upsmgOnBattery (Nota1)
Trap 11
Level 2
-upsmgReturnFromBattery (Nota1)
Trap 12
Level 1
-upsmgOnByPass
Trap 13
Level 2
-upsmgReturnFromByPass
Trap 14
Level 1
-upsmgUtilityFailure
Trap 17
Level 2
-upsmgUtilityRestored
Trap 18
Level 1
-upsmgOverLoad
Trap 21
Level 3
-upsmgLoadOK
Trap 22
Level 1
-upsmgOverTemperature (Nota1)
Trap 23
Level 3
-upsmgTemperatureOK (Nota1)
Trap 24
Level 1
-upsmgOffInProgress (Nota1)
Trap 31
Level 3
-upsmgCommunicationFailure
Trap 37
Level 3
-upsmgCommunicationRestored
Trap 38
Level 1
-upsmgRedundancyLost
Trap 65
Level 2
-upsmgRedundancyOK
Trap 66
Level 2
-upsmgProtectionLost
Trap 67
Level 2
-upsmgProtectionOK
Trap 68
Level 2
Nota1: This Information is not present with a Static Switch Cabinet unit.
If the Environment Sensor is detected , the following information are managed.:
- upsEnvironmentComFailure
Trap 53
Level 2
- upsEnvironmentComOK
Trap 54
Level 2
- upsEnvironmentTemperatureLow
Trap 55
Level 2
- upsEnvironmentTemperatureHigh
Trap 56
Level 2
- upsEnvironmentTemperatureOK
Trap 57
Level 2
- upsEnvironmentHumidityLow
Trap 58
Level 2
- upsEnvironmentHumidityHigh
Trap 59
Level 2
- upsEnvironmentHumidityOK
Trap 60
Level 2
- upsEnvironmentInput1Closed
Trap 61
Level 2
- upsEnvironmentInput1Open
Trap 62
Level 2
- upsEnvironmentInput2Open
Trap 64
Level 2
- upsEnvironmentInput2Closed
Trap 63
Level 2
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page