beautypg.com

Schneider Electric 66123 User Manual

Page 94

background image

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 94/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

mgoutputLoadPerPhase_3

%

{7,2,1,4,3,0}

mgoutputCurrent_1

deciAmps

{7,2,1,5,1,0}

mgoutputCurrent_2

deciAmps

{7,2,1,5,2,0}

mgoutputCurrent_3

deciAmps

{7,2,1,5,3,0}

upsmgOutputOnBattery (Nota2)

1(yes) 2(no)

{7,3,0}

upsmgOutputOnByPass

1(yes) 2(no)

{7,4,0}

upsmgOutputUtilityOff

1(yes) 2(no)

{7,7,0}

upsmgOutputInverterOff

1(yes) 2(no)

{7,9,0}

upsmgOutputOverLoad

1(yes) 2(no)

{7,10,0}

upsmgOutputOverTemp (Nota2)

1(yes) 2(no)

{7,11,0}

upsmgAgentIpAddress

{12,1,0}

upsmgAgentSubnetMask

{12,2,0}

upsmgAgentDefGateway

{12,3,0}

upsmgAgentType

{12,6,0}

upsmgAgentMibVersion

{12,11,0}

upsmgAgentFirmwareVersion

{12,12,0}

upsmgAgentCommUPS

1(yes) 2(no)

{12,13,0}

Nota1 :

Line Fail Cause

1

No Fail

2

Only AC Normal Voltage Ouf of Tolerance

3

Only AC Normal Frequency Ouf of Tolerance

4

AC Normal Fail

Nota2: This Information is not significative in a Static Switch Cabinet unit.