beautypg.com

3 installation in the ups, 4 sensor installation (option) – Schneider Electric 66123 User Manual

Page 16

background image

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 16/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

Ethernet port

LED

Colour

Activity

Description

ACT

Green

Off

Card not connected to the network.

On

Card connected to the network but

without activity

Flashing

Port

is

active

in

receiving

/

transmission

100M

Orange

Off

Port operating at 10Mbits/s.

On

Port operating at 100Mbits/s.

Service port (Settings/Sensor)

LED

Colour

Activity

Description

UPS

Green

Off

Card startup in progress.

Data

On

Communication with UPS in progress

Flashing

Normal operation.

Communication with the UPS is

operational

RS232

Orange

Off

Configuration menu is active

On

Normal

operation.

Configuration

menu is deactived

Flashing

Communication with the Environment

Sensor (option).

Phone port

LED

Colour

Activity

Description

UPS

Green

Off

Card not connected to phone network

Data

On

Card connected to phone network,

but no activity

Flashing

Port is sending/receiving

CD

Orange

Off

Modem is not connected

On

Modem is connected

Flashing

Modem is connecting

4.3 Installation in the UPS

The Network Management Teleservice Card (66124) can be "hot" installed in the MGE Galaxy 7000 UPS or SSC unit.

Note the card's MAC address prior to insertion

Connect the ETHERNET cable

Insert and tighten the card's retaining screws

Wait 3 min.; the card is completely operational when the green UPS Data LED flashes continuously

For Teleservice installation, the NMTC card must be installed in the SSC unit.

4.4 Sensor installation (option)

The Environment sensor is available as an option on the Network Management Card. SKU number is 66846.

The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity, status of two external

contacts. It also enables notification of alarms (e-mail, trap SNMP) according to pre-programmed thresholds.

It is connected to the Service port (Settings/Sensor) directly on the Network Management Card with a standard Ethernet cable (20 meters

maximum).

Recognition is automatic. Supervision and configuration are performed via a menu that can be accessed directly from the home page.

This manual is related to the following products: