Schneider Electric 66123 User Manual
Page 89
Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 89/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
10.3.4.9 Communication lost
Status
Modbus
Address
(word +
bit)
Value
Main UPS status
Load Powered
400
X
Load on inverter
401
X
UPS on battery
404
X
Load on AC Bypass
407
X
UPS in maintenance position
461
X
Battery Charging
493
X
UPS in Power Saving Mode
Nota: Available with NMC fw 808 and G7000 package AM
41B
X
Breaker status
Q5N circuit breaker
47B
X
Q1 circuit breaker
443
X
Q4S circuit breaker
46E
X
QF1 circuit breaker
42F
X
Q3BP circuit breaker
416
X
UPS Fault
UPS general alarm - Red Led from UPS HMI
Nota: Available with NMC fw 808 and G7000 package AN
402
X
Load not protected
41A
X
UPS Internal Communication Fault
409
1
Rectifier fault
419
X
Rectifier (PFC) fuse fault
449
X
Battery temperature fault
42A
X
End of battery runtime
406
X
Emergency Power Off
40B
X
Fan Faillure
40E
X
UPS Warning
Orange Led from UPS HMI
Nota: Available with NMC fw 808 and G7000 package AN
41C
X
Overload
40A
X
Low Battery Warning
405
X
Inverter Overload
4C2
X
Static switch overload
465
X
AC Normal Frequency Out Of Tolerance
44B
X
AC Normal Voltage Out Of Tolerance
448
X
AC bypass Out of tolerance
467
X