Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 76/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
10.3 Modbus register map
10.3.1 Detailled status table
Status description
Status to 0
Status to 1
Word
hex
Bit
0 - F
Status Familly
for
BMS design
Load powered
(protected or not protected)
No
yes
40
0
Status
Load on inverter
(UPS on AC normal or on Battery and Q5N closed)
No
yes
40
1
Status
UPS general alarm – UPS HMI Led Red (Nota 8)
No
yes
40
2
Major Fault
UPS on Battery (Nota 5)
No
yes
40
4
Status
Low Battery Warning (Nota 5)
No
yes
40
5
Major Warning
End of Battery Runtime (Nota 5)
No
yes
40
6
Major Fault
Load on bypass
No
yes
40
7
Status
Communication fault
absent
present
40
9
Major Fault
UPS overload
No
yes
40
A
Major Warning
Emergency stop
absent
present
40
B
Major Fault
Battery to be checked
or External battery monitoring fault (Nota 5)
No
yes
40
D
Minor Fault
Device ventilation fault (Nota 6)
No
yes
40
E
Major Fault
41
1
Setting
41
2
Setting
UPS type (Nota 4)
0, 5, 6 : undefine,
1 : Unitary,
2 : Modulare,
3 : parallel:
4 : SSC
41
3
Setting
Manual bypass switch (Q3BP)
Open
Closed
41
6
Status
Rectifier major failure (Nota 5)
No
Yes
41
9
Major Fault
Load not protected in unitary
Load not protected in parallel (external Q5N)
No
Yes
41
A
Major Fault
UPS in Power Saving Mode (Nota 9)
No
Yes
41
B
Status
UPS HMI Orange Led - (Nota 8)
No
Yes
41
C
Major Warning
Battery present (Nota 5)
absent
present
42
0
Setting
Battery test in progress (Nota 5)
No
yes
42
8
Status
Battery over temperature (Nota 5)
No fault
Fault
42
A
Major Fault
Battery circuit breaker (QF1) (Nota 5)
Open
Closed
42
F
Status
AC Normal switch (Q1)
Open
Closed
44
3
Status
AC Normal voltage out of tolerance (Nota 5)
No
yes
44
8
Major Warning
Rectifier (PFC) fuse fault (Nota 5)
No
yes
44
9
Major Fault
AC Normal frequency out of tolerance (Nota 5)
No
yes
44
B
Major Warning
Redundancy lost for parallel
No
yes
45
7
Major Warning
K2S fault (Nota 7)
No
yes
45
9
Minor Fault
K2S state (Nota 7)
No
yes
45
A
Status
Overlaptransfert fault on SSC
No
yes
45
B
Minor Warning
UPS on Maintenance position
No
yes
46
1
Status
AC bypass overload (Nota 7)
No
yes
46
5
Major Warning