3. SIGNALS AND WIRING

3.7 Input power supply circuit

CAUTION

Always connect a magnetic contactor (MC) between the main circuit power supply

and L

1

,

L

2

,

and L

3

of the servo amplifier, and configure the wiring to be able to shut

down the power supply on the side of the servo amplifier’s power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.

Use the trouble (ALM) to switch power off. Otherwise, a regenerative transistor

fault or the like may overheat the regenerative resistor, causing a fire.

POINT

For the power line circuit of the MR-J2S-11KA to MR-J2S-22KA, refer to
section 3.13 where the power line circuit is shown together with the servo
motor connection diagram.

3.7.1 Connection example

Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A no-fuse breaker (NFB) must be used with the input cables of the power supply.

(1) For 3-phase 200 to 230VAC power supply

RA

OFF

Emergency

ON

MC

MC

SK

NFB

MC

L

1

L

2

L

3

L

11

L

21

VDD

COM

ALM

RA

EMG

SON

SG

Servo-on

Servo amplifier

stop

3-phase

Trouble

Emergency

stop

200 to 230 VAC