beautypg.com

Adept s800 s800 User Manual

Page 35

background image

Chapter 3: System Installation

Facility Overvoltage Protection

The user must protect the robot from excessive overvoltages and voltage spikes. If the country
of installation requires a CE-certified installation, or compliance with

IEC

 1131-2, the following

information may be helpful:

IEC

1131-2 requires that the installation must ensure that

Category II overvoltages (i.e., line spikes not directly due to lightning strikes) are not exceeded.
Transient overvoltages at the point of connection to the power source shall be controlled not to
exceed overvoltage Category II, i.e., not higher than the impulse voltage corresponding to the
rated voltage for the basic insulation. The user-supplied equipment or transient suppressor
shall be capable of absorbing the energy in the transient.

In the industrial environment, nonperiodic overvoltage peaks may appear on mains power
supply lines as a result of power interruptions to high-energy equipment (such as a blown fuse
on one branch in a 3-phase system). This will cause high current pulses at relatively low
voltage levels. The user shall take the necessary steps to prevent damage to the robot system
(such as by interposing a transformer). See

IEC

1131-4 for additional information.

AC Power Diagrams

E

E

N

N

L

L

F1 10 A

Adept Cobra
s800 Inverted
Robots
1Ø 200–240 VAC

User-Supplied
AC Power Cable

Note: F1 is user-supplied, must be slow blow.

1 Ø
200–240 VAC
20 A

L = Line
N = Neutral
E = Earth Ground

Figure 3-3. Typical AC Power Installation with Single-Phase Supply

E

E

N

L3

L

L1

L2

F5 10 A

F4 10 A

Adept Cobra
s800 Inverted
Robots
1Ø 200–240 VAC

User-Supplied
AC Power Cable

Note: F4 and F5 are user-supplied, must be slow blow.

3 Ø
200–240 VAC

L = Line 1
N = Line 2
E = Earth Ground

200–240 VAC

Figure 3-4. Single-Phase Load across L1 and L2 of a Three-Phase Supply

Adept Cobra s800 Inverted Robot User's Guide, Rev H1

Page 35 of 142