Adept s800 s800 User Manual
Page 35
Chapter 3: System Installation
Facility Overvoltage Protection
The user must protect the robot from excessive overvoltages and voltage spikes. If the country
of installation requires a CE-certified installation, or compliance with
IEC
1131-2, the following
information may be helpful:
IEC
1131-2 requires that the installation must ensure that
Category II overvoltages (i.e., line spikes not directly due to lightning strikes) are not exceeded.
Transient overvoltages at the point of connection to the power source shall be controlled not to
exceed overvoltage Category II, i.e., not higher than the impulse voltage corresponding to the
rated voltage for the basic insulation. The user-supplied equipment or transient suppressor
shall be capable of absorbing the energy in the transient.
In the industrial environment, nonperiodic overvoltage peaks may appear on mains power
supply lines as a result of power interruptions to high-energy equipment (such as a blown fuse
on one branch in a 3-phase system). This will cause high current pulses at relatively low
voltage levels. The user shall take the necessary steps to prevent damage to the robot system
(such as by interposing a transformer). See
IEC
1131-4 for additional information.
AC Power Diagrams
E
E
N
N
L
L
F1 10 A
Adept Cobra
s800 Inverted
Robots
1Ø 200–240 VAC
User-Supplied
AC Power Cable
Note: F1 is user-supplied, must be slow blow.
1 Ø
200–240 VAC
20 A
L = Line
N = Neutral
E = Earth Ground
Figure 3-3. Typical AC Power Installation with Single-Phase Supply
E
E
N
L3
L
L1
L2
F5 10 A
F4 10 A
Adept Cobra
s800 Inverted
Robots
1Ø 200–240 VAC
User-Supplied
AC Power Cable
Note: F4 and F5 are user-supplied, must be slow blow.
3 Ø
200–240 VAC
L = Line 1
N = Line 2
E = Earth Ground
200–240 VAC
Figure 3-4. Single-Phase Load across L1 and L2 of a Three-Phase Supply
Adept Cobra s800 Inverted Robot User's Guide, Rev H1
Page 35 of 142