beautypg.com

Input and output functions – ITT S-DRIVE IM213 User Manual

Page 19

background image

19

Input and Output Functions

Section 8

The control terminal strips allow for a variety of input and output functions.
Warning: Turn off all power to the controller before wiring devices to the

control terminals.
Warning: Inputs RUN/STOP, HAND/AUTO, SP2/SP1 and PRESSURE DROP are

switch inputs. Do not connect power to these inputs or damage to the controller

will result. Only connect non-powered switch contacts to these inputs.
RUN/STOP: This input allows the pump/motor to be turned on and off by an

external switch. Connect the contacts of a non-powered external switch to

terminals 1 (COM) and 2 (RUN/STOP). When the switch is closed the controller

is in RUN mode (output to motor is enabled). When the switch is open the

controller is in STOP mode (output to motor is disabled).
HAND/AUTO: This input allows the controller to run the motor at full speed

without the use of a pressure transducer. This input can be controlled by an

external non-powered switch. Connect the contacts of a non-powered external

switch to terminals 3 (COM) and 4 (HAND/AUTO). When the switch is closed the

controller is in HAND mode. While in HAND mode the RUN/STOP input is used to start and stop the motor and the

pressure transducer input is ignored. When the switch is open the controller is in AUTO mode. While in AUTO mode

the controller uses the pressure transducer feedback to control the speed of the motor.
INPUT and +24V: These terminals are the transducer feedback and transducer power supply. Connect the white

lead from the transducer cable to terminal 6 (INPUT). Connect the brown lead from the transducer cable to terminal 7

(+24V). Connecting the drain (bare) wire to the chassis allows grounding of the case of the pressure transducer. The

controller is configured with a 300 PSI 4-20mA output pressure transducer.
ANALOG OUTPUT: This output is a 4-20mA signal based on motor speed (4mA = 0Hz, 20mA = 60Hz) and can be

connected to external monitoring or external control devices. Connect terminal 10 (ANALOG OUTPUT) to the 4-20mA

input of the external device. Connect terminal 9 (COM) to the negative side of the current loop on the external device.

The external device must have an input resistance (impedance) in the range of 45Ω to 250Ω. The maximum output

voltage is 24V.
SP2/SP1: This input allows the system to operate at one of 2 pressure settings. This input can be controlled by an

external non-powered switch. Connect the contacts of a non-powered external switch to terminals 5 (COM) and 11

(SP2/SP1). When the switch is closed pressure set point 2 is enabled (preset to 75 PSI when used with a 300 PSI

transducer). When the switch is open pressure set point 1 is enabled (preset to 50 PSI when used with a 300 PSI

transducer).
PRESSURE DROP: This input allows the user to select the amount of pressure drop in the system before the pump

starts. This input can be controlled by an external non-powered switch. Connect the contacts of a non-powered

external switch to terminals 5 or 9 (COM) and 12 (PRESSURE DROP). When the switch is closed the system pressure

will drop 20 PSI (when used with a 300 PSI transducer) before restarting the pump. When the switch is open the

system pressure will drop 5 PSI (when used with a 300 PSI transducer) before restarting the pump.
RUN RELAY: This output indicates when the pump/motor is running. This output can be used to control power to a

light, an alarm or other external device. When the pump/motor is off terminal 13 (RELAY1 – NO) will be open and

terminal 14 (RELAY 1 – NC) will be connected to terminal 15 (RELAY1 – COM). When the pump/motor is on terminal

13 (RELAY1 – NO) will be connected to terminal 15 (RELAY1 – COM) and terminal 14 (RELAY 1 – NC) will be open.

The relay rating is 250Vac, 5 amps maximum.
FAULT RELAY: This output indicates when the system is faulted. This output can be used to control power to a light,

an alarm or other external device. When the system is not faulted terminal 16 (RELAY2 – NO) will be open and

terminal 17 (RELAY 2 – NC) will be connected to terminal 18 (RELAY2 – COM). When the system is faulted terminal

16 (RELAY2 – NO) will be connected to terminal 18 (RELAY2 – COM) and terminal 17 (RELAY 2 – NC) will be open.

The relay rating is 250Vac, 5 amps maximum.