beautypg.com

Power supply and wiring, Conduit, wire and fuse sizing, Generator sizing – ITT S-DRIVE IM213 User Manual

Page 13: Continued)

background image

13

Power Supply and Wiring

Section 6

(continued)

Conduit, Wire and Fuse Sizing

The use of metal conduit with metal conduit connectors is recommended for all electrical connections. Use the

NEC or CEC to determine the required conduit size for the application.

Refer to the chart below for the minimum allowable wire size for each controller. Note that these wire sizes

are not adjusted for voltage drop due to long cable lengths. Refer to the wire sizing chart in the appendix to

determine the maximum length for the input cable. Refer to the motor manual for maximum output cable

length. The maximum recommended voltage drop on both input and output cable combined is 5%. Standard

wire sizing charts give maximum cable lengths for only input or output cables. Because of this the lengths

given in the table must be adjusted so the total voltage drop does not exceed 5%. For example, if the input

wire sizing chart in the appendix gives the maximum length of 400' and only 100' is used then only 25% of the

total voltage drop (1.25% drop) is used. The maximum output cable length read from the motor‘s wire sizing

chart must then be adjusted to 75% of its value so that the maximum voltage drop of 5% is not exceeded.

Use only fast acting class T fuses. The wire used for the input power connections on models SPD20300 and

SPD20300F must have a temperature rating of 90ºC minimum. All other wire must be rated 75 ºC minimum.

The chart below shows the recommended sizes for wire and fuses for each controller. Note that the wire sizes

were not adjusted for voltage drop due to long cable lengths.

Maximum Ambient Temperature

20ºC 30ºC 40ºC 50ºC

Generator Input Output Input Output Input Output Input Output

Voltage

Frame

Model Full

Load Nominal

Fuse Size Cable Cable Cable Cable Cable Cable Cable Cable

Size

Number Output Current

HP

Size

(VA)

Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG Min. AWG

1

SPD20050

17.8 5.0

30.0

7700 10 14 10 14 10 12 8 12

SPD20050F

SPD20075

26.4 7.5

40.0

11400 8 12 8 10 8 10 6 8

2

SPD20075F

SPD20100

37.0 10.0

50.0

16000

8 10 8 8 6 8 4 8

SPD20100F

SPD20150

47.4 15.0

70.0

20500

4 8 4 8 4 6 3 6

230

3

SPD20150F

SPD20200

60.6 20.0

80.0

26200

4 6 4 6 4 4 2 4

SPD20200F

SPD20250

76.0

25.0 110.0

32800

2

4

2

4

1

3

1/0

2

4

SPD20250F

SPD20300

94.0

30.0 135.0 40600

2* 3 1* 3 1* 2 1/0* 1

SPD20300F

SPD40050

8.9 5.0

15.0

7700 14 14 14 14 14 14 14 14

1

SPD40050F

SPD40075

13.2 7.5

20.0

11400 12 14 12 14 12 14 10 14

SPD40075F

SPD40100

18.5 10.0

30.0

16000 10 14 10 14 10 12 8 12

SPD40100F

460

2

SPD40150

23.7 15.0

40.0

20500 8 12 8 12 8 10 6 10

SPD40150F

SPD40200

30.3 20.0

50.0

26200 8 10 8 10 6 10 4 8

SPD40200F

SPD40250

37.5 25.0

60.0

32400

6 8 6 8 4 8 4 8

3

SPD40250F

SPD40300

47.0 30.0

70.0

40600

4 8 4 8 4 6 3 6

SPD40300F

* 90ºC Wire Required on input to controller.

Generator Sizing

Refer to the chart above to determine the minimum generator size for each controller.