Power supply and wiring – ITT S-DRIVE IM213 User Manual
Page 12

12
Power Supply and Wiring
Section 6
(continued)
Single Phase Connection
For small drives with diode rectifier front end it is possible to run a three phase output with a single phase
input. Only part of the three phase input bridge is used. Ripple current becomes 120 Hz rather than 360. This
places a greater demand on the DC filter components (capacitor bank and DC choke). The result is that the
drive must be derated to 50% current.
The chart below shows the full load output current ratings of the controller when single phase or 3 phase
power is used. If single phase input power is used the Motor Overload switches must be set to 50% or lower.
Nominal
Controller Full Load
HP Rating
Output Current Rating
Supply
Frame
Model
3 Phase
1 Phase
3 Phase
1 Phase
Voltage
Size
Number
Input
Input
Input
Input
1
SPD20050
5.0
2.0
17.8
8.1
SPD20050F
SPD20075
7.5
3.0
26.4
10.9
2
SPD20075F
SPD20100
10.0
5.0
37.0
17.8
SPD20100F
208/230
SPD20150
15.0
7.5
47.4
26.4
3
SPD20150F
SPD20200
20.0
10.0
60.6
33.0
SPD20200F
SPD20250
25.0
12.0
76.0
40.2
4
SPD20250F
SPD20300
30.0
15.0
94.0
47.4
SPD20300F
SPD40050
5.0 8.9
1
SPD40050F
SPD40075
7.5 13.2
SPD40075F
SPD40100
10.0 18.5
SPD40100F
460
2
SPD40150
15.0 23.7
SPD40150F
SPD40200
20.0 30.3
SPD40200F
SPD40250
25.0 37.5
3
SPD40250F
SPD40300
30.0 47.0
SPD40300F