Honeywell HC900 User Manual
Page 96

88
HC900 Hybrid Controller Communications User Guide
Revision 10
12/07
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
Access Notes
670D
26382
Advance Request
W
This does not apply if current style is Direct or if
Advance Active configuration parameter is set to OFF
Unsigned 16 Integer
Data Ignored
670E
26383
Input Count
R
Floating Point in Counts
6710
26385
Output On-Delay
R/W
Floating Point in Seconds
6712
26387
Output Off-Delay
R/W
Floating Point in Seconds
6714
26389
Input Enable (1-16)
R/W
Bit Packed:
Bit 0: Device #1 Enable: 0=NO, 1=YES
Bit 1: Device #2 Enable: 0=NO, 1=YES
Bit 2: Device #3 Enable: 0=NO, 1=YES
Bit 3: Device #4 Enable: 0=NO, 1=YES
Bit 4: Device #5 Enable: 0=NO, 1=YES
Bit 5: Device #6 Enable: 0=NO, 1=YES
Bit 6: Device #7 Enable: 0=NO, 1=YES
Bit 7: Device #8 Enable: 0=NO, 1=YES
Bit 8: Device #9 Enable: 0=NO, 1=YES
Bit 9: Device #10 Enable: 0=NO, 1=YES
Bit 10: Device #11 Enable: 0=NO, 1=YES
Bit 11: Device #12 Enable: 0=NO, 1=YES
Bit 12: Device #13 Enable: 0=NO, 1=YES
Bit 13: Device #14 Enable: 0=NO, 1=YES
Bit 14: Device #15 Enable: 0=NO, 1=YES
Bit 15: Device #16 Enable: 0=NO, 1=YES
6715
26390
Output Enable (1-16) R/W
Bit Packed:
Bit 0: Device #1 Enable: 0=NO, 1=YES
Bit 1: Device #2 Enable: 0=NO, 1=YES
Bit 2: Device #3 Enable: 0=NO, 1=YES
Bit 3: Device #4 Enable: 0=NO, 1=YES
Bit 4: Device #5 Enable: 0=NO, 1=YES
Bit 5: Device #6 Enable: 0=NO, 1=YES
Bit 6: Device #7 Enable: 0=NO, 1=YES
Bit 7: Device #8 Enable: 0=NO, 1=YES
Bit 8: Device #9 Enable: 0=NO, 1=YES
Bit 9: Device #10 Enable: 0=NO, 1=YES
Bit 10: Device #11 Enable: 0=NO, 1=YES
Bit 11: Device #12 Enable: 0=NO, 1=YES
Bit 12: Device #13 Enable: 0=NO, 1=YES
Bit 13: Device #14 Enable: 0=NO, 1=YES
Bit 14: Device #15 Enable: 0=NO, 1=YES
Bit 15: Device #16 Enable: 0=NO, 1=YES
6716 26391 Output
Order
Sequence #1
R
Unsigned 16 integer
6717 26392 Output
Order
Sequence #2
R
Unsigned 16 integer
6718 26393 Output
Order
Sequence #3
R
Unsigned 16 integer