background image

70

HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter

Access Notes

304A 12363 Status*

(Bit Packed)

R Bit

Packed

Bit 0:

1=Ready

1:

1=Run

2: 1=Hold

3:

1=End

4: 1=Time Units in Seconds

5: 1=Time Units in Minutes

6: 1=Time Units in Hours

7: If bit 2 Set

0: Operator hold

1: Guaranteed soak hold

8-15:

Reserved

304B

12364

Start*

W

Signed 16 bit integer
Write to location Starts Schedule;
Data ignored

304C

12365

Hold*

W

Signed 16 bit integer
Write to location Holds Schedule;
Data ignored

304D

12366

Advance*

W

Signed 16 bit integer
Write to location Advances Schedule;
Data ignored

304E

12367

Reset*

W

Signed 16 bit integer
Write to location Resets Schedule;
Data ignored

304F

12368

Time Units*

R/W

Bit Packed
Bit

0: Reserved

1: minutes

2:

hours

3-15: Unused

Scheduler Segment Fixed Register Map

A schedule can contain up to 50 segments. Each segment is made up of 48 (30 hex) registers, for a total of
2400 contiguous registers. This table contains Segment Map fixed addresses of SP Scheduler #1. See
Table 6-1 for st
arting and ending addresses (hex) for SP Scheduler #2 Addresses.

The addresses given in Table 6-16 do not necessarily apply to scheduler segments in the custom map. For
custom addresses view or print a report in HC Designer.

Table 6-16 Scheduler #1 Segment Fixed Addresses

Fixed
Start
Address
(Hex)

Fixed
Start
Register
(Decimal)

Fixed End
Address
(Hex)

Fixed End
Register
(Decimal)

Description

3200

12801

322F

12847

Scheduler #1 Segment 1

3230

12849

325F

12896

Scheduler #1 Segment 2

3260

12897

328F

12944

Scheduler #1 Segment 3

: : : :
3B30

15153

3B5F

15200

Scheduler #1 Segment 50