HC900 Hybrid Controller Communications User Guide
Revision 10
12/07
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter
Access Notes
304A 12363 Status*
(Bit Packed)
R Bit
Packed
Bit 0:
1=Ready
1:
1=Run
2: 1=Hold
3:
1=End
4: 1=Time Units in Seconds
5: 1=Time Units in Minutes
6: 1=Time Units in Hours
7: If bit 2 Set
0: Operator hold
1: Guaranteed soak hold
8-15:
Reserved
304B
12364
Start*
W
Signed 16 bit integer
Write to location Starts Schedule;
Data ignored
304C
12365
Hold*
W
Signed 16 bit integer
Write to location Holds Schedule;
Data ignored
304D
12366
Advance*
W
Signed 16 bit integer
Write to location Advances Schedule;
Data ignored
304E
12367
Reset*
W
Signed 16 bit integer
Write to location Resets Schedule;
Data ignored
304F
12368
Time Units*
R/W
Bit Packed
Bit
0: Reserved
1: minutes
2:
hours
3-15: Unused
Scheduler Segment Fixed Register Map
A schedule can contain up to 50 segments. Each segment is made up of 48 (30 hex) registers, for a total of
2400 contiguous registers. This table contains Segment Map fixed addresses of SP Scheduler #1. See
Table 6-1 for starting and ending addresses (hex) for SP Scheduler #2 Addresses.
The addresses given in Table 6-16 do not necessarily apply to scheduler segments in the custom map. For
custom addresses view or print a report in HC Designer.
Table 6-16 Scheduler #1 Segment Fixed Addresses
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Fixed End
Address
(Hex)
Fixed End
Register
(Decimal)
Description
3200
12801
322F
12847
Scheduler #1 Segment 1
3230
12849
325F
12896
Scheduler #1 Segment 2
3260
12897
328F
12944
Scheduler #1 Segment 3
: : : :
3B30
15153
3B5F
15200
Scheduler #1 Segment 50