6 variables – Honeywell HC900 User Manual
Page 63

Revision 10
HC900 Hybrid Controller Communications User Guide
55
12/07
6.6 Variables
Summary
Variables (analog or digital) are writeable parameters in HC900 attached to input pins of function blocks.
Digital Variable status is also represented in floating point: 0.0 for OFF or logic 0 and 1.0 for ON or logic
1. The Variable number in the table corresponds to the Variable number in the HC900 configuration.
You will need to access the HC900 Hybrid Control Designer configuration or corresponding configuration
printout of Tag Information Report to identify the Variable numbers desired.
Single byte writes are permitted to digital variables. A non-zero will automatically set the digital variable
to a floating point 1 and a zero write to a single register will set the digital variable to 0.
Function Code Support:
Read – Function Code 3
Write – Function Codes 6 (digital variables only), 16 (10 Hex)
The addresses given in Table 6-5 do not necessarily apply to variables in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-5 Variables
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter
Access
Notes
18C0
6337
Variable Value #1
R/W
Floating Point in Engineering Units.
18C2
6339
Variable Value #2
R/W
18C4
6341
Variable Value #3
R/W
18C6
6343
Variable Value #4
R/W
:
18C8
6345
Variable Value #5
R/W
:
18CA
6347
Variable Value #6
R/W
:
18CC
6349
Variable Value #7
R/W
:
18CE
6351
Variable Value #8
R/W
:
18D0
6353
Variable Value #9
R/W
:
18D2
6355
Variable Value #10
R/W
:
18D4
6357
Variable Value #11
R/W
:
18D6
6359
Variable Value #12
R/W
:
18D8
6361
Variable Value #13
R/W
:
18DA
6363
Variable Value #14
R/W
:
18DC
6365
Variable Value #15
R/W
:
18DE
6367
Variable Value #16
R/W
:
18E0
6369
Variable Value #17
R/W
:
18E2
6371
Variable Value #18
R/W
:
18E4
6373
Variable Value #19
R/W
:
18E6
6375
Variable Value #20
R/W
:
: : :
:
1D6E
7535
Variable Value #600
R/W
: