HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

4.2 Fixed Modbus Map

Table 4-2 and Table 4-3 list the the maximum number of Object Addresses and maximum number of registers
allowed per request. Also shown are differences between firmware versions 2.3 and 2.4.

Note 1: In versions 4.0 and higher these maximums apply to fixed map but not to the custom map.

Note 2: In versions 4.0 and higher function code 03 is not available for analog inputs.

Table 4-2 Maximum Number of Objects (fixed map only)

Note: objects marked with * have multiple parameters and therefore occupy multiple registers. For
example, a PID loop has over 40 parameters that can be accessed.

Max. No. of Objects

Object Name

C30

C50/C70/C70R

Function Code

Analog Inputs

96/12 slots v2.3
192/12 slots v2.4

640 v2.3
1280 v2.4

3: can only access first 8
slots of rack 1. Not available
in version 4.0 or higher.

4: can access all slots and
racks

Discrete Input

192/12 slots v2.3
384/12 slots v2.4

1280 v2.3
2560 v2.4

2

Discrete Output/Coil

192/12 slots v2.3
384/12 slots v2.4

1280 v2.3
2560 v2.4

1: read
5: force

Loop* 8

32

3

Variable Value

600

600

3

Set Point Programmer Value*

8

8

3

Segments per Set Point
Programmer*

50 50 3

Signal tags

2000

2000 (C50)
5000 (C70/C70R)

3

Scheduler Value*

2

2

3

Segments per Schedule*

50

50

3

Sequencer* 4

4

3

Stage* 8

8

3

Ramp* 8

8

3

Hand-Off-Auto* 16 16 3

Alternator* 6

6

3

Device Control*

16

16

3

User Defined Registers

1024

1024

3