Honeywell HC900 User Manual
Page 71

Revision 10
HC900 Hybrid Controller Communications User Guide
63
12/07
Example For Determining a Segment Register’s fixed address
Note: Custom map users should ignore this procedure. Obtain segment addresses by printing a Modbus
Register Report in HC Designer.
To change the ramp value in segment #8 of setpoint programmer #2, the register address is determined as
follows.
Step 1: Use Table 6-1 to determine the start address for setpoint programmer #2 segments. The value is
2A00 Hex.
Step 2: Calculate the offset address for segment 8 in a profile. This is calculated as:
Segment #8 offset address
=
(segment number – 1) * 8
=
(8-1) * 8
=
56 or 38 Hex
Step 3: Use the table above to determine the register offset for the ramp value. The value is 4.
Step 4: Calculate the address by adding the results of steps 1, 2, and 3 to determine the register address.
Register address
=
Setpoint program #2 segment start address
+ Segment 8 offset address
+ Ramp value register offset
=
2A00 + 38 + 4
=
2A3C