Example For Determining a Segment Register’s fixed address

Note: Custom map users should ignore this procedure. Obtain segment addresses by printing a Modbus
Register Report in HC Designer.

To change the ramp value in segment #8 of setpoint programmer #2, the register address is determined as
follows.

Step 1: Use Table 6-1 to determine the start address for setpoint programmer #2 segments. The value is

2A00 Hex.

Step 2: Calculate the offset address for segment 8 in a profile. This is calculated as:

Segment #8 offset address

=

(segment number – 1) * 8

=

(8-1) * 8

=

56 or 38 Hex

Step 3: Use the table above to determine the register offset for the ramp value. The value is 4.

Step 4: Calculate the address by adding the results of steps 1, 2, and 3 to determine the register address.

Register address

=

Setpoint program #2 segment start address
+ Segment 8 offset address
+ Ramp value register offset

=

2A00 + 38 + 4

=

2A3C