HC900 Hybrid Controller Communications User Guide
57
12/07
6.8 Set Point Programmer
Summary
The SP Programmer parameters are listed according to category related to program status and interaction, other
programmer parameters and program segment mapping.
In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:
• SP Programmer parameters (Table 6-9)
• SP Programmer Additional parameters (Table 6-9, page 60)
• SPP Programmer segments (Table 6-10).
In a custom map the above parameters may be contiguous.
Function Code Support:
Read – Function Code 3
Write – Function Code 16 (10 Hex)
Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs
A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third
party software using the parameters listed in the following table.
In creating a SP Programmer interface showing a number of segments, a graphic display might include a
table referencing the maximum number of ramp/soak segments that you will be using for your process. The
parameters to be referenced for each segment are listed in Table 6-10.