beautypg.com

Honeywell HC900 User Manual

Page 47

background image

Modbus/TCP & Modbus RTU Function Codes

Function Code 17 (11h) - Report HC900 ID

Revision 10

HC900 Hybrid Controller Communications User Guide

39

12/07

Generic Class (00) Device Mapping - Describes the I/O and feature mapping.

Number of

Records

Record

#1

Record

#2

Record

...

Record

#n

Number of Records - 1 Byte unsigned value 00-FFh (byte 23)

Record Description:

Byte

Description

00

Type of Data Element
(See Data Element Values Table Below)

01

Starting Address of Data Element Record (High)

02

Starting Address of Data Element Record (Low)

03

Number of Data Elements (High)

04

Number of Data Elements (Low)

Data Element Values Table:

Value

Description

00 Analog

Inputs

01

Not Applicable. Number of elements equals 0.

02 Discrete

Inputs

03 Discrete

Outputs

04 Control

Loops

05

Set Point Programmers

06 Variables

07

Not applicable. Number of elements equals 0.

08

Not applicable. Number of elements equals 0.

09

Not applicable. Number of elements equals 0.

10 Schedulers

11 Signal

tags

12

Signal tags List 2

13

Analog Inputs Accessed Using 3x Registers

14 Sequencers

15 Stage

16 Ramp

17

Hand Off Auto

18 Alternators

19 Device

Controls

20

Control Loops Extended

21

Setpoint Programmers Extended

22 Schedulers

Extended

23 Sequencers

Extended