HC900 Hybrid Controller Communications User Guide
49
12/07
6.4 Loop Values
About loop addresses
This table contains fixed addresses of Loop #1. See Table 6-1 for starting and ending fixed addresses
(hex) for Loop #2 through Loop #32. Each successive control loop is offset by 256 with the exception
that loop 25 has a new starting address and loop 26 – 32 are offset by 256. The loop number corresponds to
the PID block entry sequence during Hybrid Control Designer configuration. The Modbus loop number
address for a loop can also be obtained from the Hybrid Control Designer printout of Block Modbus
Addresses.
The addresses given in Table 6-3 do not necessarily apply to loops in the custom map. For custom
addresses view or print a report in HC Designer.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
Table 6-3 Loop Values
Loop type
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
PIDOn
/
Off
Carb3Pos AMB
Access Notes
0040
0065 PV
9 9 9
9
R
Floating Point in Engineering Units.
0042
0067
Remote Set Point;
SP2
9 9 9
R/W
Floating Point in Engineering Units.
When the remote setpoint source is configured as
LSP2, the value can be written.
0044
0069
Working Set Point
9 9 9
R/W
Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop’s currently
selected set point.
0046
0071 Output
9 9 9
9
R/W
Floating Point in Engineering Units.
0048
0073
PV
9 9 9
9
R
Floating Point in Engineering Units.
004A
0075
Carbon Potential block
temperature
9
R
Floating Point in Engineering Units
004C
0077
Gain #1 (Prop Band #1
if active)
9
9
R/W
Floating Point . (in units per what was configured in
the HC900: Gain or Proportional Band)
004E
0079 Direction
9 9 9
R
Floating Point
0.0=Direct; 1.0=Reverse
0050
0081
Reset #1
9
9
R/W
Floating Point in Repeats/Minute or
Minutes/Repeat.
0052
0083
Rate #1
9
9
R/W
Floating Point in Minutes
0054
0085
Cycle Time for Analog
Scan
9 9 9
9
R
Floating Point in Seconds
0056
0087
PV Low Range
9 9 9
9
R
Floating Point in Engineering Units.
0058
0089
PV High Range
9 9 9
9
R
Floating Point in Engineering Units.
005A
0091
Alarm #1 SP #1
9 9 9
9
R/W
Floating Point in Engineering Units.
005C
0093
Alarm #1 SP #2
9 9 9
9
R/W
Floating Point in Engineering Units.
0060
0097
Gain #2 (Prop Band #2
if active)
9
9 R/W
Floating
Point