5 analog input - function code 03 – Honeywell HC900 User Manual
Page 62

54
HC900 Hybrid Controller Communications User Guide
Revision 10
12/07
6.5 Analog Input - Function Code 03
Summary
Not available for versions 4.0 and later. Used to access analog input parameters for the first 8 channels of
the first 8 modules of Rack #1. (Address compatible with UMC800.)
To access any analog input channels use Function Code 04. See page 32.
Analog Input Example: AI1 through AI64. The mapping is with respect to card position starting with the
first card module position and continuing to the 8
th
module position. The first module position would be
AI1 thru AI8. The next AI card in slot 2 would be AI9 thru AI16 and so on.
Function Code Support:
Reads – Function Codes 03 (limited to the first 8 slots of Rack #1)
Table 6-4 Analog Input Value Addresses - Function Code 03
Fixed
Address
(hex)
Fixed
Register
(decimal)
Channel Number
Access
Notes
1800
6145
Analog Input #1
R
1802
6147
Analog Input #2
R
1804
6149
Analog Input #3
R
1806
6151
Analog Input #4
R
1808
6153
Analog Input #5
R
180A
6155
Analog Input #6
R
180C
6157
Analog Input #7
R
180E
6159
Analog Input #8
R
1810
6161
Analog Input #9
R
1812
6163
Analog Input #10
R
1814
6165
Analog Input #11
R
1816
6167
Analog Input #12
R
: : :
187E
6271
Analog Input #64
R
Floating Point
in Engineering
Units.
Example
Read Analog Inputs 1 and 2 from HC900 at slave address 01 using Function Code 03.
TCP:
00 03 18 00 00 04
RTU:
01 06 00 FA 00 01
CRC
CRC
Response from HC900 where AI1 = 100.0 and AI 2 = 55.32
TCP:
00 03 08 42 C8 00 00 42 5D 47 AE
RTU:
01 03 08 42 C8 00 00 42 5D 47 AE
CRC
CRC