Revision 10

HC900 Hybrid Controller Communications User Guide

45

12/07

Fixed

Start

Address

(hex)

Fixed

End

Address

(hex)

Item Description

See

section

1640 16FF Loop #23 (floating point & bit packed)

1740 17FF Loop #24 (floating point & bit packed)

1800 187F Analog

Input Value (#1-#64) First 8 slots of Rack #1 only - Function Code 03

6.5

18C0

1D6F

Variable Value (#1 - #600)

6.6

1DF0 1DF6 Time

6.7

1E00

1E0F

Set Point Programmer #1

6.8

1E10

1E1F

Set Point Programmer #2

1E20

1E2F

Set Point Programmer #3

1E30

1E3F

Set Point Programmer #4

1F00

1F3F

Set Point Programmer #1 (Additional Values)

1F40

1F7F

Set Point Programmer #2 (Additional Values)

1F80

1FBF

Set Point Programmer #3 (Additional Values)

1FC0

1FFF

Set Point Programmer #4 (Additional Values)

2000 27CF Signal Tags (#1 - #1000) (legacy)

6.9

2800

29FF

Set Point Programmer #1 Segments

6.8

2A00

2BFF

Set Point Programmer #2 Segments

2C00

2DFF

Set Point Programmer #3 Segments

2E00

2FFF

Set Point Programmer #4 Segments

3000 304F Scheduler #1 Value

6.10

3050 309F Scheduler #2 Value

3200 3B5F Scheduler #1 Segments

3B60

5A9F

Signal Tags (#1 - #4000) (HC900)

6.9

5AA0

5ABF

Sequencer #1 Parameters

6.11

5AC0

5CBF

Sequencer #1 Step 1 Table (64 steps in sequence)

6.11

5CC0

5CFF

Sequencer #1 State Table

6.11

5D00

5D1F

Sequencer #2 Parameters

6.11

5D20

5F1F

Sequencer #2 Step 1 Table (64 steps in sequence)

6.11

5F20

5F5F

Sequencer #2 State Table

6.11

5F60

5F7F

Sequencer #3 Parameters

6.11

5F80 617F Sequencer #3 Step 1 Table (64 steps in sequence)

6.11

6180 61BF Sequencer #3 State Table

6.11

6200 6227 Stage #1

6.12

6230 6257 Stage #2

6260 6287 Stage #3

6290 62B7 Stage #4

62C0 62E7 Stage

#5

62F0 6317 Stage #6

6320 6347 Stage #7

6350 6377 Stage #8

6400 642D Ramp

#1

6.13

6430 645D Ramp

#2