ProSoft Technology 5201-DFNT-DNPS User Manual
Page 73
Reference ProLinx
DNPS
♦ ProLinx Gateway
User Manual
DNP 3.0 Slave
ProSoft Technology, Inc.
Page 73 of 86
December 1, 2009
OBJECT REQUEST
RESPONSE
Obj Var
Description Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
4 16-Bit
Frozen
Delta Counter
Event Without
Time
24
Slave will return Unknown Object to
this request
5 32-Bit
Frozen
Counter Event
With Time
88
Slave will return Unknown Object to
this request
6 16-Bit
Frozen
Counter Event
With Time
72
Slave will return Unknown Object to
this request
7 32-Bit
Frozen
Delta Counter
Event With
Time
88
Slave will return Unknown Object to
this request
8 16-Bit
Frozen
Delta Counter
Event With
Time
72
Slave will return Unknown Object to
this request
30 0 Analog
Input:
All Variations
1 06
16
Slave will respond with variation 4
data
1 32-Bit
Analog
Input
1
06 129,
130
00, 01
40
Slave will return this variation (Note:
Data will only be 16-bit)
2 16-Bit
Analog
Input
1
06 129,
130
00, 01
24
Slave will return this variation
3 32-Bit
Analog
Input Without
Flag
1
06 129,
130
00, 01
32
Slave will return this variation (Note:
Data will only be 16-bit)
4 16-Bit
Analog
Input Without
Flag
1
06 129,
130
00, 01
16
Slave will return this variation
5 Short
Floating
Point Analog
Input
1
06
129,
130
00, 01
40
Slave will return this variation
6 Long
Floating
Point Analog
Input
1
06
129,
130
00, 01
72
Slave will return this variation
31 0 Frozen
Analog
Input: All
Variations
Slave will return Unknown Object to
this request
1 32-Bit
Frozen
Analog Input
40
Slave will return Unknown Object to
this request
2 16-Bit
Frozen
Analog Input
24
Slave will return Unknown Object to
this request
3 32-Bit
Frozen
Analog Input
With Time To
Freeze
88
Slave will return Unknown Object to
this request