DNP Database Offset
0 to 3999
Offset in which to place DNP data.
Binary Inputs
0 to 500
Number of words for digital input points to configure in the DNP slave device.
Each word contains 16 binary input points.
Analog Inputs
0 to 500
Number of analog input points to configure in the DNP slave device. Each point
will occupy a one-word area in the module memory.
Float Inputs
0 to 250 points
Number of floating point input points to configure in the DNP slave device. Each
point will occupy a two-word area in the module's memory.
Double Inputs
0 to 125 points
Number of double floating point input points to configure in the DNP slave device.
Each point will occupy a four word area in the module's memory.
Counters
0 to 250
Number of counter points to configure in the DNP slave device. Each point will
occupy a two-word area in the module memory. This number corresponds to the
number of frozen counters. The application maps the counters to the frozen
counters directly.
Binary Outputs
0 to 500
Number of words for digital output points to configure in the DNP slave device.
Each word contains 16 binary output points.
Analog Outputs
0 to 500
Number of analog output points to configure in the DNP slave device. Each point
will occupy a one-word area in the module memory.