DNP Database Offset

0 to 3999

Offset in which to place DNP data.

Binary Inputs

0 to 500

Number of words for digital input points to configure in the DNP slave device.
Each word contains 16 binary input points.

Analog Inputs

0 to 500

Number of analog input points to configure in the DNP slave device. Each point
will occupy a one-word area in the module memory.

Float Inputs

0 to 250 points

Number of floating point input points to configure in the DNP slave device. Each
point will occupy a two-word area in the module's memory.

Double Inputs

0 to 125 points

Number of double floating point input points to configure in the DNP slave device.
Each point will occupy a four word area in the module's memory.

Counters

0 to 250

Number of counter points to configure in the DNP slave device. Each point will
occupy a two-word area in the module memory. This number corresponds to the
number of frozen counters. The application maps the counters to the frozen
counters directly.

Binary Outputs

0 to 500

Number of words for digital output points to configure in the DNP slave device.
Each word contains 16 binary output points.

Analog Outputs

0 to 500

Number of analog output points to configure in the DNP slave device. Each point
will occupy a one-word area in the module memory.