Printing a configuration file, Dnps protocol configuration, Dnp slave – ProSoft Technology 5201-DFNT-DNPS User Manual
Page 14: Internal slave id
ProLinx DNPS ♦ ProLinx Gateway
Start Here
DNP 3.0 Slave
User Manual
Page 14 of 86
ProSoft Technology, Inc.
December 1, 2009
Printing a Configuration File
1 Select the M
ODULE
icon, and then click the right mouse button to open a
shortcut menu.
2 On the shortcut menu, choose V
IEW
C
ONFIGURATION
. This action opens the
V
IEW
C
ONFIGURATION
window.
3 On the V
IEW
C
ONFIGURATION
window, open the F
ILE
menu, and choose
P
RINT
.
This action opens the P
RINT
dialog box.
4 On the P
RINT
dialog box, choose the printer to use from the dropdown list,
select printing options, and then click OK.
1.4 DNPS
Protocol Configuration
1.4.1 [DNP
Slave]
This section provides information required to configure a slave application with
the module. Most entries contained within this section are self explanatory.
Note: A limitation of the DNP slave driver is that all points defined in the module slave database
must fit within one Class 0 poll. The maximum packet size for a Class 0 poll is 2048 bytes. A DNP
Message Size Calculator is available on the ProSoft Technology web site. This calculator will help
you ensure that the packet size fits within this requirement.
The following example shows a sample [DNP Slave] section:
Internal Slave ID
0 to 65534
This is the DNP address for the module. All messages with this address from the
master will be processed by the module.