Cd idle time, Cd random time, Cd time before receive – ProSoft Technology 5201-DFNT-DNPS User Manual
Page 19: Bi class, Ai class, Float class, Double class, Ao db trigger
Start Here
ProLinx DNPS ♦ ProLinx Gateway
User Manual
DNP 3.0 Slave
ProSoft Technology, Inc.
Page 19 of 86
December 1, 2009
CD Idle Time
0 to 32000
Defines the minimum number of milliseconds to wait before transmitting a
message after the CD signal is recognized as low.
CD Random Time
0 to 32000
Defines the range of random time to be added to the CD Idle Time before a
message will be transmitted from the slave.
CD Time Before Receive
0 to 65535
Defines the number of milliseconds to wait before receiving characters after the
CD signal is recognized as high.
BI Class
0 to 3
This parameter specifies the default class to be utilized for all the binary input
points in the DNP database that are not defined in the override list section.
AI Class
0 to 3
This parameter specifies the default class to be utilized for all the analog input
points in the DNP database that are not defined in the override list section.
Float Class
0 to 3
This parameter specifies the default class to be utilized for all the floating-point
input points in the DNP database that are not defined in the override list section.
Double Class
0 to 3
Default class for double input events.
AO DB Trigger
Yes or No
Causes the last values to not match the database values when the DNP master
sends an AO command to the module. This can be used to cause the module to
issue a conditional write command on the other protocol interface, even if the
value received is the same as received previously.