1.4.5 [DNP Slave Double Inputs]

This area is to override the class (3) and deadband for the double float database.
The point # is not the address in the analog database, but is the offset from the
start of the double floating-point database.

Point #

This is the information object address of the point.

Class

Class 1 - Highest priority

Class 2 - Middle priority

Class 3 - Lowest priority

0 - Disable.

Deadband

A range of values within which the module will avoid generating events.

1.4.6 Common

Configuration

Data Map

The

[D

ATA

M

AP

]

section allows you to copy data between areas in the gateway’s

internal database.

You can copy to 100 registers at a time, and you can configure up to 200
separate copy commands.

For example, you can copy data from the error or status tables in upper memory
to internal database registers in the User Data memory area.